The Current Transformers should conform to the following resistance tables:
For Single Stage CTs:
Part Number
X-13580253-01
X-13580253-02
X-13580253-03
X-13580253-04
X-13580253-05
X-13580253-06
X-13580253-07
X-13580253-08
X-13580253-09
X-13580253-10
Two-Stage CTs:
Two-stage CTs are used on systems that have primary voltages in excess of 600 VAC or line
currents higher than 936 amps. The first-stage CT part numbers are in the X-13580047 and X-
13580048 families. The second stage is a custom current transformer (X-13580266-01) which
has a transformation ratio of 3.6A:0.1A. The secondary of this transformer is then applied to the
Starter module.
Trane Part Number
X-13580266-01
X-13580047-01
X-13580047-02
X-13580048-01
X-13580048-02
X-13580048-03
X-13580048-04
X-13580048-05
X-13580271-01
X-13580272-01
X-13580272-02
CVHE-SB-32A
CT Size
100 A
150 A
200 A
275 A
400 A
500 A
700 A
1000 A
50 A
75 A
Resistance in Ohms
Primary: 0.020
red and brown leads
X1 to X4 0.468
X1 to X4 0.697
X1 to X4 0.031
X1 to X4 0.076
X1 to X4 0.104
X1 to X4 0.170
X1 to X3 0.255
Winding Resistance
(± ± 10%)
23 Ω
35 Ω
46 Ω
67 Ω
68 Ω
84 Ω
128 Ω
235 Ω
12 Ω
17 Ω
Secondary: 5.5
black and white leads
X1 to X3 0.374
X1 to X2 0.312
X1 to X3 0.565
X1 to X2 0.502
X1 to X3 0.028
X1 to X2 0.023
X1 to X3 0.065
X1 to X2 0.054
X1 to X3 0.086
X1 to X2 0.069
X1 to X3 0.136
X1 to X2 0.119
X1 to X2 0.204
0.026
0.031
0.044
N/A
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

CvhfCvhg

Table of Contents