External Current Limit Setpoint - Trane CVHE Troubleshooting Manual

Table of Contents

Advertisement

The following graph shows External Current Limit Setpoint with a 4-20 mA input:
120
110
100
90
80
70
60
50
40
4
5
6
The Options module DIP switches control what type of input is used. To use a 2-10 VDC signal
switch 2-1 should be in the off position. To use a 4-20 mA signal, switch 2-1 should be in the on
position.
The user must also specify the type of External Setpoint Input (4-20 mA or 2-10 VDC) in the
machine configuration menu.
CVHE-SB-32A
External Chilled Water Setpoint using a ma input
7
8
9
10
11
12
ma
13
14
15
16
17
% RLA
18
19
20
91