When two wired controllers control multiple IDUs, the wired controller can be connected to any
one IDU, provided that the connected IDU is of the same series. Meanwhile, one and only one of the
wired controllers must be set as a slave controller. At most 16 IDUs can be controlled by wired
controllers and the connected IDUs shall be within a same IDU network.
No matter when unit is turned on or off, slave controller can be set.
How to set a slave controller: hold "function" button on the designated controller for 5s, and
temperature zone displays C00. Continue holding "function" button for 5s and setting screen of
controller parameter will come out. Default temperature zone displays P00.
Press button or
of parameter values. Then the parameter value will blink. Press button or button
And then press "confirm/cancel" to finish setting.
Press "confirm/cancel" to return to the previous display until you exit from the setup of parameter
values.
Below are user's parameter settings:
Parameter
Parameter
code
name
Set up
address for
P13
wired
controller
3.9.7 Other Communication Connection Methods
For the communication connection among indoor units, between ducted type indoor unit and the
receiving light board, please refer to the indoor unit manual.
Fig.3.9.12 Two wired controllers control multiple IDU
button to select parameter code P13. Press "mode" button to switch to setup
Parameter scope
01: master wired
controller
02: slave wired
controller
Default
value
When 2 wired controllers control one or
more IDUs, they shall have different
01
addresses. Slave wired controller (02) can't
set up units' parameters except its address.
49
GMV DC Inverter VRF
to select code 02.
Remark