Gree GMV-224WM/G-X Owner's Manual page 15

Commercial air conditioners, dc inverter vrf
Hide thumbs Also See for GMV-224WM/G-X:
Table of Contents

Advertisement

No.
Name
Gas pipe
Liquid pipe
Pipe and wiring passing
hole (L×W)
Hoist hole
No.
Name
Gas pipe
Liquid pipe
Pipe and wiring passing
hole (L×W)
Hoist hole
3.2.2 Select Installation Position
Conditions for selecting the installation position
(1) Install the unit at a place where is adequate to withstand the weight of the unit and make sure
the unit would not shake or fall off.
(2) Fully consider the influence of strong winds, typhoons and earthquakes when selecting the
installation site, and strengthen the installation.
(3) The influence of flammable, explosive, corrosive gases or exhaust gases should be avoided.
(4) Ensure that there is a certain space for heat exchanging and maintenance, so that the
ventilation is smooth and the running is reliable.
(5) Outdoor units and indoor units should be as close as possible to minimize the length and
angle of the cooling pipes.
(6) Do not allow children to approach the unit. Preventive measures should be taken to prevent
children from contacting the unit.
(7) The unit should not be installed in places with high environmental pH or high voltage
fluctuations, and places such as vehicles and ships.
(8) Do not install the unit at the place where is close to the equipment that generates
electromagnetic waves. Electromagnetic waves can affect the control system and cause fault.
GMV-400WM/G-X
Φ25.4
Φ12.7
234×69
Φ50
GMV-560WM/G-X
Φ28.6
Φ15.9
234×69
Φ50
11
Pipe diameter
GMV-450WM/G-X
Φ28.6
Φ12.7
234×69
Φ50
Pipe diameter
GMV-615WM/G-X
Φ28.6
Φ15.9
234×69
Φ50
GMV DC Inverter VRF
GMV-504WM/G-X
Φ28.6
Φ15.9
234×69
Φ50
GMV-680WM/G-X
Φ28.6
Φ15.9
234×69
Φ50

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents