3.4.3 Fixation of Manifold
(1) There must be three fixing point for both horizontal and vertical installation of the Y-type
manifold.
Fixing point 1: 100 mm on the main inlet manifold from the welding point.
Fixing point 2: 200 mm on the main branched pipe from the welding point.
Fixing point 3: 250 mm on the branched pipe from the welding point.
(2) Suspend the header to the ceiling, and be sure to install the T-type manifold so that the outlet
pipes are horizontal at the lower side.
Fig.3.4.7
Fig.3.4.8
29
GMV DC Inverter VRF
Unit: mm
Unit: mm