Gree GMV-224WM/G-X Owner's Manual page 44

Commercial air conditioners, dc inverter vrf
Hide thumbs Also See for GMV-224WM/G-X:
Table of Contents

Advertisement

GMV DC Inverter VRF
specifications must be consistent with the rated power supply of the unit.
(4) The power cord must be reliably secured. It is forbidden to pull the power cord forcibly to
prevent the wiring terminal from being stressed; if the length of power cord is insufficient or
the power cord is damaged, it is forbidden to connect two power cords together. Please apply
a new power cord that meets the local regulations.
(5) The unit must be equipped with the circuit breaker and the electric leakage protection device.
The circuit breaker should have both magnetic tripping and thermal tripping functions.
(6) It is forbidden to take power from the inside of the unit, which may cause fire hazard.
(7) When wiring on site, please also refer to the circuit diagram attached on the unit. Before all
electrical installations are completed, it is forbidden to put through the power supply (circuit
breaker and electric leakage protection device on the circuit).
3.8.2 Electrical Parameters
Every unit should have corresponding short-circuit and overload protection. And also a main
switch is required to control power supply or disconnection. See Fig.3.8.1.
Please refer to the following table for the leakage protection switch and circuit breaker of outdoor
unit.
Model
GMV-224WM/G-X
GMV-280WM/G-X
GMV-335WM/G-X
GMV-400WM/G-X
GMV-450WM/G-X
GMV-504WM/G-X
GMV-560WM/G-X
GMV-615WM/G-X
GMV-680WM/G-X
GMV-735WM/G-X
GMV-785WM/G-X
GMV-839WM/G-X
GMV-895WM/G-X
circuit breaker of
Combination method
335+400
335+450
335+504
280+615
Fig.3.8.1
Capacity of
Minimum cross-
sectional area of
each
grounding wire
combination
(mm
module (A)
25
25
25
40
40
50
10.0
50
10.0
50
10.0
50
10.0
25+40
4.0+6.0
25+40
4.0+6.0
25+50
4.0+10.0
25+50
2.5+10.0
40
Recommended wire (cross-
sectional area) (mm
)
2
2.5
2.5×5
2.5
2.5×5
4.0
4.0×5
6.0
6.0×5
6.0
6.0×5
10.0×5
10.0×5
10.0×5
10.0×5
4.0×5+6.0×5
4.0×5+6.0×5
4.0×5+10.0×5
2.5×5+10.0×5
)
2

Hide quick links: