netvox RA08D Series User Manual

Wireless multifunction co2 sensor
Hide thumbs Also See for RA08D Series:

Advertisement

Quick Links

RA08D Series
Wireless Multifunction CO
Sensor
2
Wireless Multifunction CO
Sensor
2
RA08D Series User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict
confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The
specifications are subject to change without prior notice.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RA08D Series and is the answer not in the manual?

Questions and answers

Summary of Contents for netvox RA08D Series

  • Page 1 This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The...
  • Page 2: Table Of Contents

    5. Data Report ................5 5.1 Example of ReportDataCmd ..........6 5.2 Example of ConfigureCmd ..........9 5.3 ReadBackUpData .............. 11 5.4 Example of GlobalCalibrateCmd........12 5.5 Set/GetSensorAlarmThresholdCmd ........14 6. Important Maintenance Instructions ......... 15 7. RA08D Series and Sensors Configuration ....... 16...
  • Page 3: Introduction

    1. Introduction RA08D series is a Class A device based on LoRaWan open protocol. It could be used for temperature/humidity, CO , PIR, air pressure, illuminance, TVOC, PM2.5, CH2O, O , and CO detection. Data collected by sensors would be shown on the E-ink display.
  • Page 4: Setup Instruction

    4. Setup Instruction 4.1 On/Off Power on Connect to power supply Turn on The green indicator flashes once. Press and hold the function key for 5 seconds until green indicator flashes once. Reboot Then release the function key. The device will automatically shut down after the indicator flashes 10 times.
  • Page 5: Sleeping Mode

    The device is in the network: green indicator flashes once, screen refreshes once, and send a data Short press report The device is not in the network: screen refreshes once and the green indicator remains off 4.4 Sleeping Mode Sleeping period: Min Interval. The device is on and When the reportchange exceeds the setting value or the state changes, the device will send a data in the network...
  • Page 6: Data Report

    5. Data Report After powering on, the device would refresh the information on the screen and send a version packet report along with an uplink packet. Note: 1. The interval of data packets would be 10 seconds by default. When the ack = 0x01, the intervals would be 30 seconds. 2.
  • Page 7: Example Of Reportdatacmd

    Medium 500-1500 ppm Poor 1500-5000 ppm > 5000 ppm 3. Please refer Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/cmddoc to resolve uplink data. Data report configuration and sending period are as follows: Min. Interval Max. Interval...
  • Page 8 Device Report Device NetvoxPayLoadData Type Type Battery Temperature Humidity Occupy 0x01 (1Byte, (Signed 2Bytes, (2Bytes, (1Byte (2Byte ,1ppm) unit:0.1V) unit:0.01°C) unit:0.01%) 0:Un Occupy 1: Occupy) Battery 0x02 (1Byte, AirPressure (4Bytes,unit:0.01hPa) illuminance (3Bytes,unit:1Lux) unit:0.1V) Battery PM10 TVOC 0x03 (1Byte, PM2.5(2Bytes,Unit:1 ug/m (2Bytes,Unit: 1ug/m (3Bytes,Unit:1ppb) unit:0.1V)
  • Page 9 Uplink: Data #1 01A00100097A151F020C01 1st byte (01): Version byte(A0): DeviceType 0xA0 - RA08D Series byte (01): ReportType byte(00): Battery-DC power supply byte(097A): Temperature-24.26℃, 97A (Hex)= 2426 (Dec), 2426*0.01℃ = 24.26℃ byte(151F): Humidity-54.07%, 151F (Hex) = 5407 (Dec), 5407*0.01% = 54.07% byte(020C): CO -524ppm , 020C (Hex) = 524 (Dec), 524*1ppm = 524ppm...
  • Page 10: Example Of Configurecmd

    FPort: 0x07 Bytes Var (Fix = 9 Bytes) CmdID DeviceType NetvoxPayloadData CmdID– 1 byte DeviceType– 1 byte – Device Type of Device The devicetype is listed in Netvox LoRaWAN Application Devicetype.doc NetvoxPayLoadData– var bytes (Max=9bytes) Device Description Device NetvoxPayloadData Type ConfigReport...
  • Page 11 SetIRDisable 0x84 Status(0x00_success) Reserved (8Bytes,Fixed 0x00) TImeRsp GetIRDisable 0x05 Reserved (9Bytes,Fixed 0x00) TImeReq GetIRDisable IRDectionTime Reserved 0x85 IRDisableTime(2bytes Unit:s) TImeRsp (2bytes Unit:s) (5Bytes,Fixed 0x00) (1) Configure device parameters MinTime = 900s (0x0384), MaxTime = 900s (0x0384) Downlink: 01A0038403840000000000 Response: 81A0000000000000000000 (Configuration success) 81A0010000000000000000 (Configuration failure) (2) Read device configuration parameters Downlink: 02A0000000000000000000...
  • Page 12: Readbackupdata

    5.3 ReadBackUpData Fport: 0x12 Description Payload ReadBackUpData 0x01 Index(1Byte) ReadBackUpData 0x81 None RspWithOutData Temperature Humidity Occupy ReadBackUpData illuminance 0x91 (Signed 2Bytes, (2Bytes, (2Byte, (1Byte 0:Un Occupy RspWithDataBlock (3Bytes,unit:1Lux) unit:0.01°C) unit:0.01%) 1ppm) 1: Occupy) TVOC ReadBackUpData 0x92 AirPressure (4Bytes,unit:0.01hPa) (3Bytes, Reserved(3Bytes,fixed 0x00) RspWithDataBlock unit:1ppb) PM10...
  • Page 13: Example Of Globalcalibratecmd

    5.4 Example of GlobalCalibrateCmd FPort:0x0E Sensor Description CmdID PayLoad (Fix =9 Bytes) Type Channel (1Byte) Multiplier Divisor DeltValue Reserved SetGlobalCalibrate 0x01 0_Channel1 (2bytes, (2bytes, (2bytes,Signed) (2Bytes,Fixed 0x00) 1_Channel2,etc Unsigned) Unsigned) Channel (1Byte) Status SetGlobalCalibrate 0x81 0_Channel1 (1Byte, Reserved (7Bytes,Fixed 0x00) 1_Channel2,etc 0x00_success) below...
  • Page 14 (3) Calibrate the RA08D CO sensor by decreasing 100ppm SensorType: 0x06; channel: 0x00; Multiplier: 0x0001; Divisor: 0x0001; DeltValue: 0xFF9C SetGlobalCalibrateReq: Downlink: 01060000010001FF9C0000 Response: 8106000000000000000000 GetGlobalCalibrateReq: Downlink: 0206000000000000000000 Response: 82060000010001FF9C0000 (4) ClearGlobalCalibrateReq: Downlink: 0300000000000000000000 Response: 8300000000000000000000...
  • Page 15: Set/Getsensoralarmthresholdcmd

    5.5 Set/GetSensorAlarmThresholdCmd Fport:0x10 CmdID CmdDescriptor Payload (10Bytes) (1Byte) SensorType(1Byte, 0x00_Disable ALL SensorthresholdSet 0x01_Temperature, 0x02_Humidity, SensorHighThreshold SensorLowThreshold Channel(1Byte, 0x03_CO2, (4Bytes,Unit:same as (4Bytes,Unit:same as SetSensorAlarm 0x00_Channel1, 0x04_AirPressure, 0x01 reportdata in fport6, reportdata in fport6, ThresholdReq 0x01_Chanel2, 0x05_illuminance, 0Xffffffff_DISALBLEr 0Xffffffff_DISALBLEr 0x02_Channel3,etc) 0x06_PM2.5, HighThreshold) HighThreshold) 0x07_PM10, 0x08_TVOC,...
  • Page 16: Important Maintenance Instructions

    (3) Disable all sensor thresholds. (Configure the Sensor Type to 0) Downlink: 0100000000000000000000 Response: 810000000000000000000 6. Important Maintenance Instructions Kindly pay attention to the following in order to achieve the best maintenance of the product: • Do not put the device near or submerge into water. Minerals in rain, moisture, and other liquids could cause corrosion of electronic components.
  • Page 17: Ra08D Series And Sensors Configuration

    7. RA08D Series and Sensors Configuration Sensor Model (DC- Configuration RS-485 powered) CH2O PM2.5 TVOC Light Pressure Interface Standard Configuration RA08D01 support 6 sensors ⚫ Advanced Configuration 1: RA08D02 Standard Configuration ⚫ RS-485 interface ⚫ Advanced Configuration 2: RA08D03 Standard Configuration ⚫...