Ecoflam MAXFLAM 30 AB Manual page 18

Heavy oil burners
Table of Contents

Advertisement

Available languages

Available languages

EN
Service
- Troubleshooting
Fault diagnosis and repair
In the event of a malfunction, first check
that the prerequisites for correct operation
are fulfilled:
1. is the system connected to the power
supply?
2. is there oil in the tank?
3. are all shut-off valves open?
4. are all control and safety devices,
such as the boiler thermostat, low-water
detector, limit switch, etc.
adjusted correctly?
If the malfunction persists, use the
following table.
It is not permitted to repair any
components relevant to safety. These
Red blink code of
signal lamp (LED))
2 blinks
3 blinks
4 blinks
5 blinks
6 blinks
7 blinks
8 blinks
9 blinks
10 blinks
18
www.ecoflam-burners.com
components must be replaced by parts
with the same order number.
Only use original spare parts.
NB: after each operation:
• under normal operating conditions
(doors closed, hood fitted, etc.), check
combustion and check the individual
lines for leaks.
• Record the results in the relevant
documents.
Error code table
«AL» at
Possible cause
term. 10
on
No establishment of flame at the end of «TSA»
- Faulty or soiled fuel valves - Faulty or soiled flame detector
- Poor adjustment of burner, no fuel - Faulty ignition equipment
on
Free
on
Extraneous light on burner startup
on
Free
on
Free
on
Too many losses of flame during operation
(limitation of the number of repetitions)- Faulty or soiled fuel valves.
- Faulty or soiled flame detector - Poor adjustment of burner.
on
Time supervision oil preheater
- Oil preheater failed 5 times during prepurging
on
Free
off
Wiring fault or internal fault, output contacts,other faults.
on
3 times temporary fault of the output contacts
420010405502

Advertisement

Table of Contents
loading

This manual is also suitable for:

Maxflam 50 abMaxflam 30 ab tc 230-400-50Maxflam 30 ab tl 230-400-50Maxflam 50 ab tc 230-400-50Maxflam 50 ab tl 230-400-503142600 ... Show all

Table of Contents