P
RODUCT DESCRIPTION
The
DIMENSION
CP-Series
power supplies in a medium price range without
compromising quality, reliability and performance.
The CP-Series is part of the DIMENSION power supply
family. The most outstanding features of CP20 are the
high efficiency, advanced inrush current limitation,
active PFC and the wide operational temperature
range.
The CP20.242 features an enhanced DC input voltage
range.
The device also offers PowerBoost: Power reserves
of 20%, which may even be used continuously at
temperatures up to +45°C.
High immunity to transients and power surges as
well as low electromagnetic emission, a DC-OK relay
contact and a large international approval package
for a variety of applications makes this unit suitable
for nearly every situation.
O
RDER NUMBERS
Description:
Power supply CP20.242-xx
Order Number:
CP20.242
Enhanced DC input
Accessories:
ZM10.WALL
Wall/Panel mount bracket
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
Aug. 2022 / Rev. 2.1 DS-CP20.242-xx-en
units
are
high-end
www.pulspower.com
P
OWER SUPPLY
• AC 100-240V Wide-range input
• Width only 48mm
• Efficiency up to 95.6%
• Excellent partial load efficiency
• 20% Output power reserves (PowerBoost)
• Safe Hiccup
PLUS
overload mode
• Easy fuse breaking - 3 times nominal current for 12ms
• Active power factor correction (PFC)
• Minimal inrush current surge
• Full power between -25°C and +60°C
• Remote ON / OFF function
• DC-OK relay contact
• 3 Year warranty
S
HORT-FORM DATA
Output voltage
DC 24V
Adjustment range 24-28Vdc
Output current
20-17.1A
15-13A
Derate linearly between +60°C and +70°C
PowerBoost
24A
Linear decrease to nominal power
between +45°C and +60°C
Input voltage AC
AC 100-240V
Mains frequency
50-60Hz
Input current AC
4.26 / 2.23A
Power factor
0.996 / 0.98
Input voltage DC
DC 110-300V
Input current DC
4.64 / 1.66A
AC Inrush current
10 / 4.5A
Efficiency
94.2 / 95.6%
Power losses
29.6 / 22.1W
Hold-up time
32 / 32ms
Temperature range -25°C to +70°C
Size (w x h x d)
48x124x127mm
Weight
830g
M
AIN APPROVALS
For details and the complete approval list, see chapter 20.
UL 61010-2-201
CP20.242
1AC 24V 480W
Nominal
Factory setting 24.1V
Up to +60°C ambient
At +70°C ambient
Up to +45°C ambient
-15% / +10%
±6%
At 120 / 230Vac
At 120 / 230Vac
±20%
At 110 / 300Vdc
At 120 / 230Vac
peak
At 120 / 230Vac
At 120 / 230Vac
At 120 / 230Vac
Without DIN rail
1 / 31

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DIMENSION CP20.242 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Puls DIMENSION CP20.242

  • Page 1 CP20.242 1AC 24V 480W OWER SUPPLY • AC 100-240V Wide-range input • Width only 48mm • Efficiency up to 95.6% • Excellent partial load efficiency • 20% Output power reserves (PowerBoost) • Safe Hiccup PLUS overload mode • Easy fuse breaking - 3 times nominal current for 12ms •...
  • Page 2: Table Of Contents

    CP20.242 Index Intended Use............21 Regulatory Product Compliance......21 Installation Instructions........22 Physical Dimensions And Weight...... 22 AC-Input.............. 23 Accessories............23 DC-Input.............. 23.1 ZM10.Wall - Wall/Panel Mount Bracket.. 23 Input Inrush Current.......... 23.2 UF20.241 - Buffer Module...... 23 Output..............23.3 YR40.241 - Redundancy Module....
  • Page 3: Intended Use

    CP20.242 Intended Use This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control, process control, monitoring and measurement equipment or the like. Do not use this device in equipment, where malfunctioning may cause severe personal injury or threaten human life without additional appropriate safety devices, that are suited for the application.
  • Page 4: Ac-Input

    CP20.242 AC-Input The device is suitable to be supplied from TN-, TT- or IT-mains networks with AC voltage. For suitable DC supply voltages see chapter 4. AC input nom. AC 100-240V AC input range 85-264Vac 264-300Vac Occasionally for maximal 500ms Allowed voltage L or N to max.
  • Page 5: Dc-Input

    CP20.242 DC-Input ±20% DC input nom. DC 110-300V DC input range 88-360Vdc DC input current typ. 4.64A At 110Vdc, 24V, 20A typ. 1.66A At 300Vdc, 24V, 20A Allowed voltage (+) or (−) max. 375Vdc Continuous, according to IEC 60664-1 input to earth Turn-on voltage typ.
  • Page 6: Input Inrush Current

    CP20.242 Input Inrush Current An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage. The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. AC 100V AC 120V AC 230V Inrush current I max.
  • Page 7: Output

    CP20.242 Output The output provides a SELV/PELV/EST1 rated voltage, which is galvanically isolated from the input voltage. The output is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors, such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance >1F are connected to the output, the unit might charge the capacitor in an intermittent mode.
  • Page 8 CP20.242 Fig. 6-1: Output voltage vs. output current, typ. Fig. 6-2: Dynamic overcurrent capability, typ. Fig. 6-3: Short-circuit on output, Hiccup PLUS mode, typ. Fig. 6-4: Output voltage in “parallel use” mode, typ. All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. Aug.
  • Page 9: Hold-Up Time

    CP20.242 Hold-up Time The hold-up time is the time during which a power supply’s output voltage remains within specification following the loss of input power. The hold-up time is output load dependent. At no load, the hold-up time can be up to several seconds. The green DC-OK LED is also on during this time.
  • Page 10: Dc-Ok Relay Contact

    CP20.242 DC-OK Relay Contact This feature monitors the output voltage on the output terminals of a running power supply. Contact closes As soon as the output voltage reaches typ. 90% of the adjusted output voltage level. Contact opens As soon as the output voltage dips more than 10% below the adjusted output voltage. Short dips will be extended to a signal length of 100ms.
  • Page 11: Efficiency And Power Losses

    CP20.242 Efficiency and Power Losses AC 100V AC 120V AC 230V Efficiency typ. 93.6% 94.2% 95.6% At 24V, 20A typ. 93.5% 94.1% 95.5% At 24V, 24A (PowerBoost) Average efficiency typ. 93.2% 93.8% 25% at 5A, 25% at 10A, 25% at 15A, 25% at 20A Power losses typ.
  • Page 12: Lifetime Expectancy

    CP20.242 10. Lifetime Expectancy The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h).
  • Page 13: Functional Diagram

    CP20.242 12. Functional Diagram Fig. 12-1: Functional diagram All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. Aug. 2022 / Rev. 2.1 DS-CP20.242-xx-en www.pulspower.com 13 / 31...
  • Page 14: Terminals And Wiring

    CP20.242 13. Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field- and factory wiring. CP20.242 Input Output Signal Terminals Type Screw terminals Screw terminals Push-in terminals Solid wire max. 6mm max. 6mm max. 1.5mm Stranded wire max.
  • Page 15: Front Side And User Elements

    CP20.242 14. Front Side And User Elements Input Terminals N, L Line input PE (Protective Earth) input Output Terminals Two identical (+) poles and three identical (−) poles Positive output (−) Negative output (return) Output Voltage Potentiometer Open the flap to adjust the output voltage. Factory set.: 24.1V DC-OK LED (green) On, when the output voltage is >90% of the adjusted output voltage.
  • Page 16: Emc

    CP20.242 15. EMC The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments. The output is allowed to be grounded or floating. Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not suited to supply a local DC power network in residential, commercial and light-industrial environments.
  • Page 17: Environment

    CP20.242 16. Environment Operational temperature -25°C to +70°C The operational temperature is the same as the ambient or surrounding temperature. It is defined as the air temperature 2cm below the device. Storage temperature -40°C to +85°C For storage and transportation Output derating 12W/K Between +60°C and +70°C...
  • Page 18: Protection Features

    CP20.242 17. Protection Features Output over-voltage typ. 30.5Vdc The output shuts down and automatically attempts to protection restart for three times. If after the third time the restart still fails, the output is switched off permanently until the max. 32Vdc line input is disconnected for a second.
  • Page 19: Dielectric Strength

    CP20.242 19. Dielectric Strength The output voltage is floating and has no ohmic connection to the ground. The output is insulated to the input by a double or reinforced insulation. Type and routine tests are conducted by the manufacturer. Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down).
  • Page 20: Approved, Fulfilled Or Tested Standards

    CP20.242 20. Approved, Fulfilled or Tested Standards IEC 62368 CB Scheme Certificate IEC 62368-1 - Audio/video, information and communication technology equipment - Safety requirements Output safety level: ES1 IEC 61010 CB Scheme Certificate IEC 61010-2-201 - Electrical Equipment for Measurement, Control and Laboratory Use - Particular requirements for control equipment UL 61010 UL Certificate...
  • Page 21: Regulatory Product Compliance

    CP20.242 21. Regulatory Product Compliance EU Declaration of The CE mark indicates conformance with the European Conformity – EMC directive – Low-voltage directive (LVD) – RoHS directive WEEE Regulation Manufacturer's Declaration EU Directive on Waste Electrical and Electronic Equipment Registered in Germany as business to business (B2B) products.
  • Page 22: Physical Dimensions And Weight

    CP20.242 22. Physical Dimensions And Weight Width 48mm Height 124mm Depth 127mm The DIN rail depth must be added to the unit depth to calculate the total required installation depth. Weight 830g DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm. Housing material Body: Aluminium alloy Cover: Zinc-plated steel...
  • Page 23: Accessories

    CP20.242 23. Accessories 23.1. ZM10.WALL - WALL/PANEL MOUNT BRACKET This bracket is used to mount the devices on a wall/panel without utilizing the DIN rail. The bracket can be mounted without detaching the DIN rail brackets from the power supply. Fig.
  • Page 24: Yr40.241 - Redundancy Module

    CP20.242 23.3. YR40.241 - REDUNDANCY MODULE The YR40.241 is a dual redundancy module, which can be used to build 1+1 or N+1 redundant systems. The device is equipped with two 20A nominal input channels, which are individually decoupled by utilizing MOSFET technology. The output can be loaded with a nominal 40A continuous current.
  • Page 25: Application Notes

    CP20.242 24. Application Notes 24.1. PEAK CURRENT CAPABILITY The device can deliver peak currents (up to several milliseconds) which are higher than the specified short term currents. This helps to start current demanding loads. Solenoids, contactors and pneumatic modules often have a steady state coil and a pick-up coil.
  • Page 26: Output Circuit Breakers

    CP20.242 24.2. OUTPUT CIRCUIT BREAKERS Standard miniature circuit breakers (MCB’s or UL 1077 circuit breakers) are commonly used for AC-supply systems and may also be used on 24V branches. MCB’s are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe regardless of whether the MCB opens or not.
  • Page 27: Parallel Use To Increase Output Power

    CP20.242 24.3. PARALLEL USE TO INCREASE OUTPUT POWER Power supplies can be paralleled to increase the output power. The output voltage of all devices shall be adjusted to the same value (±100mV) in “Single Use” mode with the same load conditions on all units, or the units can be left with the factory settings.
  • Page 28: Parallel Use For Redundancy

    CP20.242 24.4. PARALLEL USE FOR REDUNDANCY Please note that there are variants with built-in redundancy are available in the CP20 series. Check CP20.241-Rx units. 1+1 Redundancy: Power supplies can be paralleled for redundancy to gain higher system availability. Redundant systems require a certain amount of extra power to support the load in case one device fails.
  • Page 29: Series Operation

    CP20.242 24.5. SERIES OPERATION Power supplies of the same type can be connected in series for higher output voltages. It is possible to connect as many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a potential above 60Vdc must be installed with a protection against touching.
  • Page 30: Use In A Tightly Sealed Enclosure

    CP20.242 24.8. USE IN A TIGHTLY SEALED ENCLOSURE When the power supply is installed in a tightly sealed enclosure, the temperature inside the enclosure will be higher than outside. In such situations, the inside temperature defines the ambient temperature for the power supply. The power supply is placed in the middle of the box, no other heat producing items are inside the box.
  • Page 31: Mounting Orientations

    CP20.242 24.9. MOUNTING ORIENTATIONS Mounting orientations other than input terminals on the bottom and output on the top require a reduction in continuous output power or a limitation in the maximum allowed ambient temperature. The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation. The following curves give an indication for allowed output currents for altitudes up to 2000m.

Table of Contents