Safety Components - Riello 663 T80 Installation, Use And Maintenance Instructions

Light oil burners
Table of Contents

Advertisement

Flame sensor
Clean the glass cover from any dust that may have accumulated.
To remove the sensor 1)(Fig. 37) pull it outwards with force; it is
inserted only by pressure.
Flame inspection window
Clean the viewing port as required (Fig. 38).
Possible pump and/or coupling replacement
Carry out the fitting following the instructions in the Fig. 39.
Flame presence check
Check the level of the flame detection signal with the "Check
Mode" function from the flame control: LEDs from 2 to 6 indicate
the flame signal level, respectively.
See paragraph "LED lamps: burner operating status" on
page 33.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.
20167399
Maintenance
D874
Fig. 37
D484
Fig. 38
D1108
Fig. 39
30
Combustion
Carry out an analysis of the combustion flue gases. Significant
differences with respect to the previous measurements indicate
the points where more care should be exercised during
maintenance.
If the combustion values measured before starting maintenance
do not comply with applicable Standards or do not indicate
efficient combustion, consult the table below or contact our
Technical Support Service to implement the necessary
adjustments.
EN 267
Theoretical max CO
2
0 % O
2
15.2
9.2.3

Safety components

The safety components must be replaced at the end of their life
cycle indicated in Tab. L. The specified life cycles do not refer to
the warranty terms indicated in the delivery or payment
conditions.
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam) (if present)
Oil valve (solenoid)(if
present)
Oil regulator (if present)
Oil pipes/ couplings
(metallic) (if present)
Flexible hoses (if present)
Fan impeller
GB
Air excess
Max. output
Min. output
  1,2
  1,3
CO
% Calibration
2
 = 1.2
 = 1.3
12.6
11.5
Life cycle
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
15 years
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years
5 years or 30,000 pressurised
cycles
10 years or 500,000 start-ups
CO
mg/kWh
 100
Tab. K
Tab. L

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rl 38/mRl 50/mRl 28/m664 t80665 t80

Table of Contents