Problems - Causes - Remedies signalled by LED indicators
No.
Faults
46
Off-specification mains voltage
47
UV: Internal fault
48
Supervisor processor fault
49
Main processor fault
50
Ignition feedback fault
51
Pilot feedback fault
52
Piloted valve feedback fault
53
Actuator feedback waiting time
expired
54
Direct ignition valve feedback fault
55
Internal processor fault
56
UV: false flame during operation
57
FR: false flame during operation
58
T8 inlet fault
59
Internal hardware fault
60
Local reset fault
61
Open POC fault
62
UV: strong UV flame fault
63
Internal hardware fault
Fault explanation
No.
Faults
1
Post-diagnostics fault
2
Local reset
3
Combustion air fan fault
4
Supervisor processor
diagnostics fault
5
FR- No flame at the end of the
nd
2
safety time (MTFI)
6
FR: internal circuit fault
7
Internal communication fault
8
Remote reset
9
FR: internal fault
10
Main processor fault
11
Data memory test fault
12
Data memory test fault
13
Mains voltage or frequent fault
14
Internal processor fault
15
Internal processor fault
16
st
No flame: 1
safety time (PTFI)
17
Wiring fault
18
Safety relay fault
19
Combustion airflow switch fault
in the rest position
20167399
LED 1
LED 2
Cause
Initial power diagnostics fault
Make sure that the status of inlets and
outlets is correct upon ignition
The user started the manual reset or the
reset switch is faulty
No Air Check signal (T14) during the bleed
cycle or Air Check signal loss during the
burner operation
The system detected the presence of
voltage on T16, T17, T18 or T19 at the
wrong moment or there is no voltage when
necessary
No flame at the end of the second safety
time
Internal fault
Internal fault
The user pressed the remote reset button or
the reset switch is discontinuous/dynamic
Internal fault
Internal fault
Internal fault
Internal fault
Off-specification power supply voltage and/
or frequency
Internal fault
Internal fault
No flame at the end of the first safety time
The system detected the presence of
voltage on critical terminals (T16, T17, T18
or T19) at the wrong moment or there is no
voltage when necessary
Internal fault
Open the circuit upon T13 start-up
36
GB
LED 3
LED 4
LED 5
Solution
Check T12, T13 and T14
Check T21 inlet or reset for normal
operation
Check the fan or the air pressure switch
Check the wiring and make sure that the
system is operating on a single-phase line
(50/60Hz)
Inspect the system, check the gas pressure,
inspect the flame detection electrode, check
the wiring, etc.
Replace the control device
Replace the control device
Check the remote switch
Replace the control device
Replace the control device
Replace the control device
Replace the control device
Check the input power supply
Replace the control device
Replace the control device
Inspect the system, check the gas pressure,
check the UV scanner, check the wiring,
etc.
Inspect the wiring and make sure that the
system is operating on a single-phase line
(50/60Hz)
Replace the control device
Check the wiring for the air pressure switch
LED 6
LED 7
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Red
Tab. O