Siemens SIMOTICS 1LE8 Operating Instructions Manual page 210

Low-voltage motors shaft heights 80 ... 355
Table of Contents

Advertisement

Commissioning
7.2 Switching on
4. During the test run, check and document the following:
– Check whether it is running smoothly.
– Document the voltage, current and power values. As far as possible, document the
– If this is possible using the available measuring equipment, check the bearing and
– Check the motor for noise or vibrations on the bearings or bearing shields as it runs.
5. In case of uneven running or abnormal noise, switch off the motor. As the motor runs down,
identify the cause.
– If the mechanical operation improves immediately after the motor is switched off, then
– If the mechanical running does not improve immediately after switching the motor off,
208
corresponding values of the driven machine.
stator winding temperatures until they have reached steady-state values.
the cause is magnetic or electrical.
then the cause is mechanical.
- Imbalance of the electrical motor or the driven machine
- The machine set has not been adequately aligned
- The motor is being operated at the system resonance point. System = motor, base
frame, foundation, ...
NOTICE
Serious damage to the motor
If the vibration values in operation are not maintained in accordance with DIN ISO
10816-3, then the motor may get damaged.
• During operation, observe the vibration values in accordance with
DIN ISO 10816-3.