Immergas VICTRIX TERA V2 24 PLUS EU Instructions And Recommendations page 33

Hide thumbs Also See for VICTRIX TERA V2 24 PLUS EU:
Table of Contents

Advertisement

Extensions for Ø 60/100 vertical kit (Fig. 21)
The kit with this configuration can be extended up to a max. verti-
cal straight length of 14.4 m including the terminal. This configu-
ration corresponds to a resistance factor of 100. In this case specif-
ic extensions must be requested.
Mounting the vertical kit with aluminium tile Ø 80/125 (Fig. 22)
To install the kit Ø 80/125 one must use the flanged adapter kit in order to install the flue system Ø 80/125.
1. Install the flanged adaptor (2) on the central hole of the appliance, positioning gasket (1) with the circular projections downwards in
contact with the appliance flange.
Imitation aluminium tile installation:
2. Tighten the concentric flange with the screws in the kit.
3. Replace the tiles with the aluminium sheet (4), shaping it to ensure that rainwater runs off.
4. Position the fixed half-shell (5) on the aluminium tile;
5. Insert the intake-exhaust terminal (7);
6. Fit the Ø 80/125 concentric terminal pipe with the male side (smooth) to the female side of the adapter (1) (with lip seals) up to the end
stop, making sure that the wall sealing plate (3) has been fitted; this will ensure sealing and joining of the elements making up the kit.
7
6
5
4
3
2
1
The adapter kit includes (Fig. 22):
C
33
N°1 Gasket (1)
N°1 Adapter Ø 80/125 (2)
The Kit Ø 80/125 includes (Fig. 22):
N°1 Wall sealing plate (3)
N°1 Aluminium tile (4)
N°1 Fixed half-shell (5)
N°1 Mobile half-shell (6)
N°1 Concentric intake/exhaust pipe Ø 80/125 (7)
The remaining kit components must not be used