Victrix Tera V2 24 Plus EU
Gas type
G20
G31
Gas type
G20
G31
Victrix Tera V2 35 Plus EU
Gas type
G20
G31
Gas type
G20
G31
If a Hydrogen ready installation is envisaged for H
O
values in the table above.
2
In addition to yearly maintenance, one must also check the energy efficiency of the thermal system, with frequency and proce-
dures that comply with the indications of the technical regulations in force.
When adjusting Nominal Q., if the O
ments are required.
CO
to nominal Q.
2
9,2 (9,1 ÷ 9,5)
10,2 (10,0 ÷ 10,4)
O
at Nominal Q.
2
4,4 (4,6 ÷ 3,9)
5,3 (5,6 ÷ 5,0)
CO
to nominal Q.
2
9,0 (8,9 ÷ 9,3)
10,2 (10,1 ÷ 10,4)
O
at Nominal Q.
2
4,8 (5,0 ÷ 4,2)
5,3 (5,5 ÷ 5,0)
values are not reached with the gas flow regulator completely open, no further adjust-
2
CO
to ignition Q.
2
9,1 (9,0 ÷ 9,4)
10,2 (10,0 ÷ 10,4)
O
at Ignition Q.
2
4,6 (4,8 ÷ 4,1)
5,3 (5,6 ÷ 5,0)
CO
to ignition Q.
2
9,0 (8,9 ÷ 9,3)
10,2 (10,0 ÷ 10,4)
O
at Ignition Q.
2
4,8 (5,0 ÷ 4,2)
5,3 (5,6 ÷ 5,0)
percentages up to 20%, all gas valve calibration operations must refer to the
2
CO
to minimum Q.
2
8,5 (8,3 ÷ 8,7)
9,7 (9,5 ÷ 9,9)
O
at Minimum Q.
2
5,7 (6,0 ÷ 5,3)
6,1 (6,4 ÷ 5,8)
CO
to minimum Q.
2
8,5 (8,2 ÷ 8,6)
9,6 (9,4 ÷ 9,8)
O
at Minimum Q.
2
5,7 (6,2 ÷ 5,5)
6,3 (6,6 ÷ 6,0)
65