MSRK 2024
v.1.0
MSRK 27,6V/2A/OC
Buffer, switch mode power supply module
with technical outputs.
EN**
Edition: 2 from 11.05.2015
Supersedes the edition: 1 from 11.06.2014

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MSRK 2024 and is the answer not in the manual?

Questions and answers

Summary of Contents for Pulsar MSRK 2024

  • Page 1 MSRK 2024 v.1.0 MSRK 27,6V/2A/OC Buffer, switch mode power supply module with technical outputs. EN** Edition: 2 from 11.05.2015 Supersedes the edition: 1 from 11.06.2014...
  • Page 2: Table Of Contents

    MSRK2024 Features:  DC 27,6V/2A uninterruptible power supply  EPS technical output indicating AC power loss  high efficiency 89% – OC type  PSU technical output indicating PSU failure – OC type  low voltage ripple  LoB technical output indicating battery low voltage ...
  • Page 3: Block Diagram

    MSRK2024 1.2. Block diagram (fig.1) Fig.1. Block diagram of the PSU module 1.3. Description of components and connectors PSU module. Table 1. Elements of the PSU module pcb (fig. 2). Element no. Description ; pins - configuration of UVP battery protection function ...
  • Page 4: Specifications

    MSRK2024 Fig.2. View of the PSU module. 1.4 Specifications: - electrical parameters (tab.3) - mechanical parameters (tab.4) - operating parameters (tab.5) Electrical parameters (tab. 3). Mains supply 33V AC 100VA min. (e.g. AWT042) Current up to 3,5 A max.
  • Page 5: Installation

    MSRK2024 - PSU; output indicating DC absence / PSU - OC type: 50mA max. module failure Normal operation: L state (0V), failure: hi-Z state, - LoB output indicating battery low voltage - OC type, 50mA max. Normal operation (U >23V): L state (0V),...
  • Page 6: Operating Status Indication

    MSRK2024 11. Check the output voltage (the PSU voltage without load should amount to 27,2V÷ 27,8V, during battery charging 22V÷ 27,6V). If the value of the voltage requires adjustment, it should be set by the V potentiometer, monitoring the voltage at the AUX output of the PSU module.
  • Page 7: Operation And Use

    MSRK2024 4. Operation and use. 4.1 Overload or short circuit of the PSU module output. The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load (load 110% ÷ 150% @25ºC of the PSU module power), the output voltage is of the PSU module exceeds I automatically cut off and indicated by the green diode going off.
  • Page 8 THE GENERAL WARRANTY CONDITIONS 1. Pulsar (the manufacturer) grants a five-years warranty for the equipment, counted from the device’s production date. 2. The warranty includes free-of-charge repair or replacement with an appropriate equivalent (the selection is at the manufacturer’s discretion) if the malfunction is due to the manufacturer, includes manufacturing or material defects, unless such...