6. Inspection and maintenance

Proper functioning of the ventilation system, its effectiveness and its
service life can only be assured if the system is inspected and
maintained in accordance with the following regulations. These
regulations are based on normal operating conditions.

6.1. Inspection and maintenance schedule

Advance Plus inspection schedule
Check for unusual noises coming from
Noise
the ventilation unit, air valves and ducts
G3 filter
G4 filter
Check for soiling
F7 filter
Check for soiling and condensation water
Ventilation unit
leakage
Motor module
Check for soiling/imbalance
Bypass valve
Check functioning and for soiling
Air valves
Check for soiling
Ducts
Check for soiling
Advance Plus maintenance schedule
Clean (first 3 months)
G3 filter
Replace (with G4 or F7)
Clean
G4 filter
Replace
Clean
F7 filter
Replace
Clean outside
Ventilation unit
Clean condensate hose
Motor module
Clean
Bypass valve
Clean
Air valves
Clean
Ducts
Clean
Battery for RF control
Replace
switch
ä
Caution!
If the ventilation system is being used under harsh operating
conditions or in a very dirty environment, extra maintenance
may be required.
User
Installer
6 months
1 year
1 week
9 months
1 year
6 months
1 year
6 months
1 year
1 year
1 year
3 months
1 year
4 years
User
Installer
Where
1 week
necessary
Where
3 months
necessary
Where
9 months
necessary
Where
18 months
necessary
Where
6 months
necessary
Where
12 months
necessary
3 months
1 year
1 year
4 years
1 year
3 months
1 year
8 years
Where
Where
necessary
necessary
29