Menus; Home Screen - Watts tekmar 289 Installation, Operation And Maintenance Manual

Smart boiler control
Table of Contents

Advertisement

Menus

Home Screen

Parameter
CONDENSATE
(-55 .0 to 65 .0°C)
OUTDOOR
(-35 .0 to 130°C)
TARGET
(38 .0 to 104 .5 °C)
PRESSURE
TIME REMAINING
(HEAT ON)
TIME REMAINING
(HEAT OFF)
ROOM TARGET
BOOST
EARLY START
SMART SETBACK
DOMESTIC HOT
WATER
OUTDOOR
(-35 .0 to 130°C)
CONDENSATE
(-55 .0 to 65 .0°C)
INDOOR
PRESSURE
COMBUSTION AIR
WARM WEATHER
SHUT DOWN
Auto, Hand, Max
OVERRIDE
Range
-32 to 266°F
The condensate return temperature .
-67 to 149°F
The outdoor air temperature .
100 to 220°F
The condensate return must reach the steam established target to the Heat On cycle .
0 .0 to 15 .0 psi
The steam system pressure .
(0 to 105 kPa)
00:00:00 to
The time that the boiler is on during the heating cycle .
02:00:00
00:00:00 to
The time that the boiler is off during the heating cycle .
02:00:00
35 to 100°F
The desired room temperature when an indoor sensor is installed .
(1 .5 to 38 .0°C)
Off or On
Dot is green when Boost is active .
Off or On
Dot is green when Early Start is active .
Off or On
Dot is green when Smart Setback is active .
Off or On
Dot is green when DHW call is active .
-67 to 149°F
The outdoor air temperature .
-32 to 266°F
The condensate return temperature .
35 to 100°F
The indoor sensor temperature .
(1 .5 to 38 .0°C)
1 .0 to 15 .0 psi
The steam system pressure .
(0 to 105 kPa)
Off or On
Dot is green when combustion air damper is open .
Off or On
Dot is green when warm weather shut down is in effect .
The manual override status .
Heat, Off
Description
HOME SCREEN
SYSTEM INPUTS
SYSTEM STATUS
17

Advertisement

Table of Contents
loading

Table of Contents