Settings (5 of 5)
Parameter
BOILER PLANT
NO HEAT ALERT
ENABLE
BOILER PLANT NO
HEAT ALERT
HIGH PRESSURE
ALERT
FLUE
TEMPERATURE
ALERT
Default: 392°F (200 .0°C)
INDOOR
TEMPERATURE
COLD ALERT
ENABLE
INDOOR
TEMPERATURE
COLD ALERT
INDOOR
TEMPERATURE HOT
ALERT ENABLE
INDOOR
TEMPERATURE HOT
ALERT
BOILER 1 SERVICE
HOURS ALERT
BOILER 1 SERVICE
CYCLES ALERT
BOILER 2 SERVICE
HOURS ALERT
BOILER 2 SERVICE
CYCLES ALERT
STEP 1
STEP 2
REQUIRE
PASSCODE
PASSCODE
22
Range
Off or On
Select if an alert is triggered if the condensate return temperature does not increase .
Requires a condensate sensor to be installed .
Default: Off
Set the amount of time of no temperature change while boilers are firing after which
5 .0 to 80 .0 minutes
the control triggers a boiler plant no heat alert notification . Requires a condensate
Default: 60 .0 minutes
sensor to be installed .
0 .0 to 15 .0 psi
(0 to 105 kPa)
Set the threshold above which the control triggers a high pressure alert notification .
Default: 15 .0 psi
(105 kPa)
100 to 392°F
(38 .0 to 200 .0°C)
Set the threshold above which the control triggers a flue temperature alert notification .
Off or On
Select if an alert is triggered if the indoor temperature falls below the threshold .
Requires an indoor sensor to be installed .
Default: Off
32 to 100°F
Set the threshold below which the control triggers an indoor temperature cold alert
(0 .0 to 38 .0 °C)
notification . Requires an indoor sensor to be installed .
Default: 38°F (3 .5°C)
Off or On
Select if an alert is triggered if the indoor temperature exceeds the threshold . Requires
an indoor sensor to be installed .
Default: Off
32 to 100°F
Set the threshold below which the control triggers an indoor temperature hot alert
(0 .0 to 38 .0 °C)
notification . Requires an indoor sensor to be installed .
Default: 78°F (25 .5°C)
1000 to 25000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
Default: 5000 hours
1 to 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
Default: 25000 cycles
1000 to 25000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
Default: 5000 hours
1 to 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
Default: 25000 cycles
N/A
Set a personal passcode . This is required when a passcode has already been set .
Confirm the personal passcode . This is required when a passcode has already
N/A
been set .
Off or On
Select if a passcode is required to enter the Home screen .
Default: Off
N/A
Select to change the personal passcode . Redirects user to Steps 1 and 2 .
Description
ALERTS
SECURITY