Settings (5 Of 5) - Watts tekmar 289 Installation, Operation And Maintenance Manual

Smart boiler control
Table of Contents

Advertisement

Settings (5 of 5)

Parameter
BOILER PLANT
NO HEAT ALERT
ENABLE
BOILER PLANT NO
HEAT ALERT
HIGH PRESSURE
ALERT
FLUE
TEMPERATURE
ALERT
Default: 392°F (200 .0°C)
INDOOR
TEMPERATURE
COLD ALERT
ENABLE
INDOOR
TEMPERATURE
COLD ALERT
INDOOR
TEMPERATURE HOT
ALERT ENABLE
INDOOR
TEMPERATURE HOT
ALERT
BOILER 1 SERVICE
HOURS ALERT
BOILER 1 SERVICE
CYCLES ALERT
BOILER 2 SERVICE
HOURS ALERT
BOILER 2 SERVICE
CYCLES ALERT
STEP 1
STEP 2
REQUIRE
PASSCODE
PASSCODE
22
Range
Off or On
Select if an alert is triggered if the condensate return temperature does not increase .
Requires a condensate sensor to be installed .
Default: Off
Set the amount of time of no temperature change while boilers are firing after which
5 .0 to 80 .0 minutes
the control triggers a boiler plant no heat alert notification . Requires a condensate
Default: 60 .0 minutes
sensor to be installed .
0 .0 to 15 .0 psi
(0 to 105 kPa)
Set the threshold above which the control triggers a high pressure alert notification .
Default: 15 .0 psi
(105 kPa)
100 to 392°F
(38 .0 to 200 .0°C)
Set the threshold above which the control triggers a flue temperature alert notification .
Off or On
Select if an alert is triggered if the indoor temperature falls below the threshold .
Requires an indoor sensor to be installed .
Default: Off
32 to 100°F
Set the threshold below which the control triggers an indoor temperature cold alert
(0 .0 to 38 .0 °C)
notification . Requires an indoor sensor to be installed .
Default: 38°F (3 .5°C)
Off or On
Select if an alert is triggered if the indoor temperature exceeds the threshold . Requires
an indoor sensor to be installed .
Default: Off
32 to 100°F
Set the threshold below which the control triggers an indoor temperature hot alert
(0 .0 to 38 .0 °C)
notification . Requires an indoor sensor to be installed .
Default: 78°F (25 .5°C)
1000 to 25000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
Default: 5000 hours
1 to 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
Default: 25000 cycles
1000 to 25000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification .
Default: 5000 hours
1 to 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification .
Default: 25000 cycles
N/A
Set a personal passcode . This is required when a passcode has already been set .
Confirm the personal passcode . This is required when a passcode has already
N/A
been set .
Off or On
Select if a passcode is required to enter the Home screen .
Default: Off
N/A
Select to change the personal passcode . Redirects user to Steps 1 and 2 .
Description
ALERTS
SECURITY