Pressure Switch Adjustment; Air Pressure Switch - Check Co; Maximum Gas Pressure Switch; Minimum Gas Pressure Switch - Riello 20074125 Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

6.7

Pressure switch adjustment

6.7.1

Air pressure switch - check CO

Adjust the air pressure switch (Fig. 33) after performing all other
burner adjustments with the air pressure switch set to the start of
the scale.
With the burner operating at min. output, increase adjustment
pressure by slowly turning the relative knob clockwise until the
burner locks out.
Then turn the knob anti-clockwise by about 20% of the set point
and repeat burner starting to ensure it is correct.
If the burner locks out again, turn the knob anticlockwise a little
bit more.
In conformity with the standard, the air pressure
switch must prevent the air pressure falling below
80% of the adjusted value and the CO in the flue
gases exceeding 1% (10,000 ppm).
WARNING
To check this, insert a combustion analyser into
the chimney, slowly close the fan suction inlet (for
example with cardboard) and check that the burn-
er locks out, before the CO in the fumes exceeds
1%.
6.7.2

Maximum gas pressure switch

Adjust the maximum gas pressure switch (Fig. 34) after perform-
ing all other burner adjustments with the maximum gas pressure
switch set to the end of the scale.
With the burner operating at maximum output, lower adjustment
pressure by slowly turning the relative knob anticlockwise until
the burner locks out.
Turn the knob clockwise by 0.2 kPa (2 mbar) and repeat the start-
up of the burner.
If the burner locks out again, turn the knob clockwise again by
0.1 kPa (1 mbar).
6.7.3

Minimum gas pressure switch

Adjust the minimum gas pressure switch (Fig. 35) after perform-
ing all the other burner adjustments with the pressure switch set
to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner locks out.
Then turn the knob anticlockwise by 0.2 kPa (2 mbar) and repeat
burner start-up to ensure it is uniform.
If the burner locks out again, turn the knob anticlockwise again by
0.1 kPa (1 mbar).
1 Kpa = 10 mbar
WARNING
Start-up, calibration and operation of the burner
33
GB
D3854
Fig. 33
Fig. 34
D3856
Fig. 35
D3855
20079034

Advertisement

Table of Contents
loading

Table of Contents