Particulate Contamination - Lenovo 7X19 Setup Manual

Hide thumbs Also See for 7X19:
Table of Contents

Advertisement

Table 1. Specifications, Type 7X18 and 7X19 (continued)
Environment
Operating systems
Note: To maintain component reliability, system performance might vary at ambient temperature higher than
35°C while all the fans are functioning. With one fan failing, system performance might vary at ambient
temperature higher than 27°C.

Particulate contamination

Attention: Airborne particulates (including metal flakes or particles) and reactive gases acting alone or in
combination with other environmental factors such as humidity or temperature might pose a risk to the
device that is described in this document.
Risks that are posed by the presence of excessive particulate levels or concentrations of harmful gases
include damage that might cause the device to malfunction or cease functioning altogether. This
specification sets forth limits for particulates and gases that are intended to avoid such damage. The limits
must not be viewed or used as definitive limits, because numerous other factors, such as temperature or
ThinkSystem SR850 complies with ASHRAE Class A2 specifications. Depending on the
hardware configuration, some models comply with ASHRAE Class A3 and Class A4
specifications. System performance may be impacted when operating temperature is
outside ASHRAE A2 specification.
• Air temperature:
– Operating
– ASHRAE Class A2: 10°C to 35°C (50°F to 95°F); the maximum ambient
temperature decreases by 1°C for every 300 m (984 ft) increase in altitude
above 900 m (2,953 ft).
– ASHRAE Class A3: 5°C to 40°C (41°F to 104°F); the maximum ambient
temperature decreases by 1°C for every 175 m (574 ft) increase in altitude
above 900 m (2,953 ft).
– ASHRAE Class A4: 5°C to 45°C (41°F to 113°F); the maximum ambient
temperature decreases by 1°C for every 125 m (410 ft) increase in altitude
above 900 m (2,953 ft).
– Server off: 5°C to 45°C (41°F to 113°F)
– Shipment/storage: -40°C to 60°C (-40°F to 140°F)
• Maximum altitude: 3,050 m (10,000 ft)
• Relative Humidity (non-condensing):
– Operating
– ASHRAE Class A2: 8% to 80%; maximum dew point: 21°C (70°F)
– ASHRAE Class A3: 8% to 85%; maximum dew point: 24°C (75°F)
– ASHRAE Class A4: 8% to 90%; maximum dew point: 24°C (75°F)
– Shipment/storage: 8% to 90%
• Particulate contamination
Attention: Airborne particulates and reactive gases acting alone or in combination
with other environmental factors such as humidity or temperature might pose a risk to
the server. For information about the limits for particulates and gases, see
"Particulate contamination" in ThinkSystem SR850 Maintenance Manual.
Supported and certified operating systems:
• Microsoft Windows Server
• VMware ESXi
• Red Hat Enterprise Linux
• SUSE Linux Enterprise Server
References:
• Complete list of available operating systems:
• OS deployment instructions:
https://lenovopress.lenovo.com/osig
"Deploy the operating system" on page
.
126.
.
Chapter 1
Introduction
7

Advertisement

Table of Contents
loading

This manual is also suitable for:

7x18Thinksystem sr850

Table of Contents