8.1 Configuration

8.1 Configuration

8.1.1 Setting Communication Conditions

Configuration
Setting items
Communication
mode
Station no.
Baud rate
Data length
Parity
Stop bit
RS/CS
Send waiting time
(set value × 0.01
ms)
Start code STX
Terminator setting
Terminator judgment
time
(set value × 0.01
ms)
Modem initialization
(Note 1)
In MODBUS communication, the following setting items need not be specified.
Start code, terminator setting, terminator judgment time, modem initialization, PLC link setting
8-2
Default
Specification range
MEWTOCOL-COM
MODBUS RTU
1
1 to 247
300 / 600 / 1200 / 2400 /
9600
4800 / 9600 / 19200 /
38400 / 57600 / 115200
8 bit
8 bit
Odd
None / Odd / Even
1 bit
1 bit
Invalid
Invalid / Valid
0
0 to 10000
Invalid
-
CR
-
0
-
Do not initialize
-
Remark
Specify "MODBUS RTU".
Set a specific station no. for PLC to
be connected to the PLC link. Set a
value that does not overlap with
other devices.
The setting must be done according
to the devices connected.
The setting must be done according
to the devices connected. In
general, 8-bit length, even parity,
and 1-stop bit is used.
Set this when it is necessary to
delay response to the partner device
in slave communication.
Use the unit in the default setting as
indicated on the left.