Pump Pressure; Air Damper Adjustment; Main Air Damper; Secondary Air Damper - Riello 744T0K Installation, Use And Maintenance Instructions

Table of Contents

Advertisement

7.4

Pump pressure

The pump leaves the factory set for kerosene working.
10 bar: maximum pressure for kerosene.
7.5

Air damper adjustment

The air damper is set in factory.
This regulation is purely indicative. Each installation however,
has its own unpredictable working conditions: actual nozzle out-
put; positive or negative pressure in the combustion-chamber,
the need of excess air, etc.
All these conditions may require a different air damper setting.
The air setting is performed by mean of two inde-
pendent dampers (Fig. 16 and Fig. 17).
WARNING
7.5.1

Main air damper

The main air damper A)(Fig. 16) can be set in two positions for
12/15 and 18 kW;
To set the positions of the damper, proceed as follows:
 remove the secondary air damper B) loosing the screws 1);
 loosen the screw 2) and rotate the main air damper A) to the
required position;
 re-tighten the screw 2) and put back the secondary air
damper B).
7.5.2

Secondary air damper

The purpose of this damper B)(Fig. 17) is to perform a fine-tuning
of the inlet air.
Tuning of this device is possible acting of the screw 3)(Fig. 17).
7.6

Electrodes setting

The position of the electrodes cannot be regulat-
ed.
In case of failure, check that the measurements as
WARNING
shown on Fig. 18 are respected.
Before removing or assembling the nozzle, loosen the screw
A)(Fig. 18) and move the electrodes ahead.
Start-up, calibration and operation of the burner
E9172
4 ±
0.3 mm
D5230
19
GB
20075077
B
3
A
2 - 2.5
Fig. 16
Fig. 17
mm
Fig. 18
20074517

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rdb2.2 firebird 12/1820074461

Table of Contents