Environmental; Mechanical; Compliances; Servicing - NewMar RM2048HE Installation Manual

48v rectifier
Table of Contents

Advertisement

Input to Output
Input to Chassis
Output to Chassis
3.3

Environmental

Operating Ambient Temperature
Rated
Range
Humidity
Altitude
3.4

Mechanical

Dimensions (W, H, D)
Weight
Shipping Dimensions (W, H, D) 120 mm, 52 mm, 325 mm
Shipping Weight
3.5

Compliances

Safety
Electrostatic Discharge
Radiated Radio Frequency
AC Harmonics
AC Flicker and Fluctuation
Other
Due to continual product development, specifications are subject to change without prior notice.

4 Servicing

If the rectifier develops an operational fault, or is damaged in any way, an Authorized Service Center should service
it immediately.
4.1

Warnings

This rectifier contains no user serviceable components.
Do not operate the rectifier if the covers are damaged or removed in any way.
-
The rectifier contains voltages that may be lethal even after the input supply
has been removed
-
The rectifier contains components at High Temperatures that may cause
burns if touched
Rectifier Installation Manual
4000 V DC
3500 V DC (VDR to chassis removed)
2100 V DC
25 ± 5 ºC
-20 ºC to 70 ºC (maximum power derates above 45 ºC)
5 – 98% RH (non-condensing)
< 2000 m above sea level
111.5 mm, 44 mm (1U), 282 mm overall (260 mm shelf)
1.5 kg
1.6 kg
EN 60950
CISPR 24
CISPR 22
EN 61000-3-2
EN 61000-3-3
CE & RoHS compliant
DANGER
Do not disassemble the rectifier.
Page 9 of 10

Advertisement

Table of Contents
loading

Table of Contents