ABB SPEF 3A2 C User Manual And Technical Description page 8

Fault indicator
Table of Contents

Advertisement

8
Analog outputs
Voltage range
Minimum load impedance
Response delay
Inaccuracy
External control inputs
External control voltage level
Typical control current of input circuit
Data transmission
Transmission mode
Protocol
Selectable data transfer rates
Power supply
Supply
Power consumption
Test voltages
For output relays:
Insulation test according to IEC 60255-5
Impulse test according to IEC 60255-5
Insulation resistance test according to IEC 60255-5
Disturbance tests
Current inputs are measured with the
connection box SPEC 3 and a connection cable
of at least two meter. High frequency interference
test voltage, inputs and output between them-
selves and to the fault indicator frame as per:
Common mode acc. to IEC 60255-22-1
Differential mode acc. to IEC 60255-2-1
Common mode acc. to ANSI C37.90.1-1989
Fast transient test IEC 60255-22-4, cl. III
Electrostatic discharge test acc. to
IEC 60255-22-2, cl. III
- contact discharge
- air discharge
Environmental conditions
Enviromental condition tests are made on
SPEF 3A2 C without current sensors.
Specified ambient service temperature range
Transport and storage temperature range
Temperature influence on the operating values over
the specified ambient service temperature range
Climatic environmental tests
- dry heat test acc. to IEC 60068-2-2
- dry cold test acc. to IEC 60068-2-1
- damp heat test acc. to IEC 60068-2-30
Degree of protection by enclosure of the
device case as per IEC 60529
Mass of the fault indicator
0...5 V
10 kΩ
< 500 ms
5% or ± 30 mV when current > 5 A
I
load
5% or ± 30 mV
I
0
∆I ± 200 mV when I
phase
) max ≥ 10 A
(I
or I
or I
L1
L2
L3
18...30 Vdc
10 mA
serial bus
SPA bus
4800 or 9600 Bd
20...30 V dc
1.5...3 W (depending on relays
and indicators)
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5 J
>100 MΩ, 500 Vdc
2.5 kV, 1 MHz
1 kV, 1 MHz
2.5 kV, 1 MHz
2 kV
6 kV
8 kV
-10°C to +55°C
-40°C to +70°C, 72 h + 72 h
<0.02%/°C
+55°C/16h
-10°C/16h
RH=93%, 55°C, 6 cycles
IP 20
about 1.3 kg