20
When the fault indicator module SPEF 3A2 C
is linked to a control data communicator over
the SPA bus, the module will provide time-
stamped events e.g. to a printer. The events are
printed out in the format: time, user-specified
text and event code. The events are generated on
start, alarm, resetting and output relay opera-
tion. Every function has its own code designa-
tion from E1...E18. Masking parameters can be
used to inhibit events from being generated by
one or several functions. An event buffer is
Code Event
E1
Start of stage I>
E2
Start of stage I> reset
E3
Alarm of stage I>
E4
Alarm of stage I> reset
E5
Start of stage I
>
0
E6
Start of stage I
> reset
0
E7
Alarm of stage I
0
E8
Alarm of stage I
0
Default checksum for mask V155
Starting of stage ∆I>
E9
Starting of stage ∆I> reset
E10
Alarming of stage ∆I>
E11
Alarming of stage ∆I> reset
E12
Default checksum for mask V156
E13
Output signal I> alarm activated
E14
Output signal I> alarm reset
E15
Output signal I
0
E16
Output signal I
0
Output signal ∆I> alarm activated
E17
Output signal ∆I> alarm reset
E18
Default checksum for mask V157
E50
Restarting
E51
Overflow of event register
E52
Temporary interruption in data communication
E53
No response from the module
over the data communication
E54
The module responds again
over the data communication
0 Not included in the event reporting
1 included in the event reporting
*
No code number
-
Cannot be programmed
Note!
The event codes E52...E54 are only generated
by the data communicator unit. (SACO 100M,
SRIO 1000M, etc.)
>
> reset
> alarm activated
> alarm reset
capable of memorizing up to eight events. If
more than eight events occur before the content
of the buffer has been sent to the communicator
an overflow event "E51" is generated. This
event has to be reset by writing a command "0"
to parameter C over the SPA bus. More infor-
mation about the serial communication over the
SPA bus can be found in the document "SPA-
BUS COMMUNICATION PROTOCOL",
34 SPACOM 2 EN1.
Number
representing
the event
1
2
4
8
16
32
64
128
1
2
4
8
1
2
4
8
16
32
*
*
*
*
*
Default value
of the factor
1
0
1
0
1
0
1
0
85
1
0
1
0
5
1
0
1
0
1
0
21
-
-
-
-
-