Fault indicator
Table of Contents

Advertisement

22
Data
Memorized start of stage I>
Memorized alarm of stage I>
Memorized start of stage I
Memorized alarm of stage I
Memorized start of stage ∆I>
Memorized alarm of stage ∆I>
Memorized I> alarm relay
Memorized I
> alarm relay
0
Memorized ∆I> alarm relay
SETTING VALUES
Start value for stage I>
Operate time for stage I>
Start value for stage I
>
0
Operate time for stage I
0
Start value for stage ∆I>
Operate time for stage t∆>
Checksum of switchgroup SGF1
Checksum of switchgroup SGF2
Checksum of switchgroup SGB
Range selector for max phase
analog output
Range selector for I
analog output
0
RECORDED AND MEMORIZED PARAMETERS
Line current on phase L1 at alarm
Line current on phase L2 at alarm
Line current on phase L3 at alarm
Neutral current I
at start or alarm
0
Phase unbalance ∆I at start or alarm
Duration of start of stage I>
Duration of start of stage I
Duration of start of stage ∆I>
Time stamp of alarm
HH.MM;SS.sss
Number of starts of stage I>
Number of starts of stage I
Number of starts of stage ∆I>
Alarming phase
Operation indicator
Code
direction
O21
O22
>
O23
0
>
O24
0
O25
O26
O27
O28
O29
S1
S2
S3
>
S4
S5
S6
S7
S8
S9
S10
S11
V11,V31...91 R
V12,V32...92 R
V13,V33...93 R
V14,V34...94 R
V15,V35...95 R
V16,V36...96 R
V17,V37...97 R
0
V18,V38...98 R
V19,V39...99 R
V1
>
V2
0
V3
V4
V5
Data flow Value range
R
0 = I>-stage not started
1 = I>-stage started
R
0 = I>-stage not
1 = I>-stage alarmed
R
0 = I
>-stage not started
0
1 = I
>-stage started
0
R
0 = I
>-stage not alarmed
0
1 = I
>-stage alarmed
0
0 = ∆I>-stage not started
R
1 = ∆I>-stage started
0 = ∆I>-stage not alarmed
R
1 = ∆I>-stage alarmed
R
0 = signal not active
1 = signal active
R
0 = signal not active
1 = signal active
R
0 = signal not active
1 = signal active
R,W(P)
30.0...300 A
R,W(P)
0.06...300 s
R,W(P)
2...20 A
R,W(P)
0.10...300 s
R,W(P)
10...60%
R,W(P)
1.00...300 s
R,W(P)
0...255
R,W(P)
0...255
R,W(P)
0...255
R,W(P)
10, 20, 50,100, 200, 500 A
R,W(P)
5, 10, 20, 50, 100 A
0...700 A
0...700 A
0...700 A
0...70 A
0...100 %
0...100 %
0...100 %
0...100 %
Y Y - M M - D D
R
0...255
R
0...255
R
0...255
R
1 = I>(L3), 2 = I>(L2),
4 = I>(L1), 8 = I
R
0...6
alarmed
>, 16 = ∆I
0