Recorded data

16
When the fault indicator provides an alarm
signal, the current values at the moment of the
alarm, the duration of the start of the different
units and other parameters are stored in a
five-place memory stack. A new event moves the
old values up one place and adds the new value
to the first place of the stack which contains
registers 1...8. Five events are memorized - if a
sixth alarm occurs, the oldest set of values will be
lost. A master reset (pressing the push-buttons
Register
Recorded information
1
Line phase current L1 (n) measured in ampere
Event (n-1) value of line phase current L1
Event (n-2) value of line phase current L1
Event (n-3) value of line phase current L1
Event (n-4) value of line phase current L1
2
Line phase current L2 (n) measured in ampere
Event (n-1) value of line phase current L2
Event (n-2) value of line phase current L2
Event (n-3) value of line phase current L2
Event (n-4) value of line phase current L2
3
Line phase current L3 (n) measured in ampere
Event (n-1) value of line phase current L3
Event (n-2) value of line phase current L3
Event (n-3) value of line phase current L3
Event (n-4) value of line phase current L3
4
Duration of the latest starting situation (n) of overcurrent stage I> as a percentage
of the set operating time t>. When the concerned stage has alarmed the counter
reading is 100 per cent.
Duration of event (n-1) starting of stage I>
Duration of event (n-2) starting of stage I>
Duration of event (n-3) starting of stage I>
Duration of event (n-4) starting of stage I>
Number of startings of the stage I> in the range 0...255.
5
Neutral current measured in ampere
Event (n-1) value of neutral current
Event (n-2) value of neutral current
Event (n-3) value of neutral current
Event (n-4) value of neutral current
6
Duration of the latest starting situation (n) of stage I
of the set operate time t
reading is 100 per cent. //
Duration of event (n-1) starting of stage I
Duration of event (n-2) starting of stage I
Duration of event (n-3) starting of stage I
Duration of event (n-4) starting of stage I
Number of startings of the stage I
Phase unbalance ∆I in per cent of the highest phase current //
7
Event (n-1) value of phase unbalance ∆I
Event (n-2) value of phase unbalance ∆I
Event (n-3) value of phase unbalance ∆I
Event (n-4) value of phase unbalance ∆I
RESET and PROGRAM simultaneously) of
the relay erases all the contents of the register
blocks.
The left-most red digit displays the register
address and the other three digits the recorded
information.
Note! A symbol "//" in the text indicates that the
following item is found in a submenu.
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
>. When the concerned stage has alarmed the counter
0
> //
0
> //
0
> //
0
> //
0
> in the range 0...255.
0
//
//
//
//
//
//
//
> expressed as a percentage
0