Central Remote Controller
When the connected outdoor unit is Super Multi u series (U series)
Follow the wiring specifications in the table below even when there is a mix of U series and non-U series in the connected indoor
units or remote controllers.
Wiring specifications
Item
Wire diameter
Wire type
Wire types that can be used
REQUIREMENT
When wiring the control wiring between indoor and outdoor units (Uv line)/control wiring between outdoor units (Uc line) and
the central control wiring (Uh line), use the same wire type and diameter for each line.
Using a mixture of different wire types and diameters may cause a communication error.
System diagram
Central control
device
<U series>
Outdoor unit
(Super Multi
u series)
<U series>
Indoor unit *
<U series>
Remote
controller *
* The wiring specifications in the system diagram above are the same even when the indoor unit or remote controller are other
than the U series.
LINK (Uh)
U 3 U 4
U 3 U 4
U h
U c
U v
U 1
U 2
U 1
U 5 U 6
U 1 U 2
U 1 U 2
U4
U v
A
B
U6
Communication line
Central control wiring (Uh line)
AWG16: Up to 3281 ft (1000 m)
AWG14: Up to 6560 ft (2000 m)
2-core, non-polar
Shielded wire
[Central control wiring (Uh line)]
L1 = Up to 6560 ft (2000 m)
[Control wiring between indoor and outdoor units (Uv
line)/Control wiring between outdoor units (Uc line)]
L2 = Up to 3281 ft (1000 m)
(L3+L4) = Up to 3281 ft (1000 m)
U 3 U 4
U 3 U 4
U h
U h
U c
U v
U v
U 2
U 1
U 2
U 5 U 6
U 1 U 2
U4
U4
U v
U v
A
B
U6
Installation Manual
U c
U 5 U 6
U 1 U 2
U4
U v
A
B
A
B
U6
U6
-EN
9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tcb-sc640u-ul

Table of Contents