Indicator Led - M-system R7C-DC16A Instruction Manual

Npn transistor output module, 16 points
Hide thumbs Also See for R7C-DC16A:
Table of Contents

Advertisement

INDICATOR LED

■ STATUS INDICATOR LED
PWR RUN ERR
SD
ON
ON
FL
FL
ON
ON
FL
FL
ON
ON
FL
FL
ON
ON
FL
OFF
ON
ON
FL
OFF
ON
ON
OFF
FL
ON
ON
OFF
FL
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
OFF
FL
FL
ON
OFF
FL
FL
ON
OFF
FL
OFF
ON
OFF
FL
OFF
ON
OFF
OFF
FL
ON
OFF
OFF
FL
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
OFF ON/OFF Faulty Baud Rate and/or Station Address setting
OFF
OFF
OFF
OFF
OFF = OFF, ON = ON, FL = Flashing
---- = Inconceivable in normal operations (e.g. LED failure)
■ DISCRETE I/O STATUS INDICATOR LED
Discrete I/O modules including those for extensions have LED indicators showing I/O signal status.
Contact ON
: LED ON
Contact OFF : LED OFF
RD
STATUS
ON
Communicates normally with occasional CRC errors due to noise interference.
ON
Communicates normally but the Baud Rate and/or Station Address switches failed.
ERR LED flashes approximately in 0.5 second intervals.
OFF
----
ON
CRC error found in the received data. Unable to respond.
OFF
----
ON
Normal communication
OFF
----
ON
Unable to receive data addressed to the station.
OFF
----
ON
Performs the interval-timed responses but CRC error found in receiving the refresh
data.
OFF
----
ON
CRC error found in the data addressed to the station.
OFF
----
ON
Link is not started.
OFF
----
ON
No data addressed to the station. Or unable to receive data addressed to the station
due to noise interference. (Missing parts of the data sent from the master)
OFF
Unable to receive data due to wire breakdown
OFF
Power input removed. Or power supply failure.
R7C-DC16A
EM-780-G Rev.4
P.  / 8

Advertisement

Table of Contents
loading

Table of Contents