Power Board Initial Settings

Not Install: Ordinarily, keep this set to "Not Install" (initial
setting).
Install: Free topology terminal resistor (51Ω) for the
LonWorks communication lines.
Install
S002
Power board
CN005
(when AC 100-120V
power is connected)
L
N
100-120 V~
200-240 V~
When AC 200-240V power is connected, connect the power
transformer primary-side to CN006. When AC 100-120V power is
connected, connect the power transformer primary-side to CN005.
(It is connected to CN006 when the unit is shipped from the plant.)

Power Board Wiring

Earth for inter-unit control wiring
LON communication
lines (2)
LON communication
line (2) (reserve)
LON communication
lines (1)
LON communication
line (1) (reserve)
Inter-unit
control lines
Inter-unit
control line (reserve)
Earth for power wiring
• The LonWorks communication lines can be connected to either
(1) or (2) in the above figure. The results are the same.
• Do not run the inter-unit control lines, the LonWorks
communication lines, and the power cables through the same
conduit, or place the cables near one another. Doing so can cause
the system to malfunction.
• Before turning the power on, follow the instruction in Power
Board Initial Settings.
• When using the spare inter-unit cotrol line, connect [1] and [3] at
CN002.
• When using the spare LON communication line, connect [1] and
[3] or [4] and [6] at CN003.
Not Install
ON
Power switch
S001
OFF
CN006 (when AC 200-240V
power is connected)
Power transformer primary-side
6
CN003
Power board
1
3
L
N
CN002
1
100-120 V~
200-240 V~

Wiring Procedure

• Connect the power supply lines to the L and N power
supply terminals.
(the power suplly neutral to the N terminal.)
• Connect an earth ground line to the screw.
Lon communication wiring
L
Use this screw when connecting the shield
for the Inter-unit control wiring to ground
Inter-unit control wiring

Main Circuit Board

Neuron ID label
IC002
S005
S003
Address SW
LD009
S004
Indoor unit enabling SW
N
Power supply
S001
S002
LD001~LD008
Data
COM
S006
Setting SW