ABB Fimer PVI-10.0/12.5-TL-OUTD Product Manual page 77

Table of Contents

Advertisement

Parameter
Description
Set U>>
Grid over-voltage (OV) threshold (extended range)
Set U<<
Grid under-voltage (UV) threshold (extended range)
Set F>>
Grid over-frequency (OF) threshold (extended range)
Set F<<
Grid under-frequency (UF) threshold (extended range)
Set U>
Grid over-voltage (OV) threshold (restricted range)
Set U> (10Min)
Grid over-voltage (OV) threshold (average grid voltage value)
Set U<
Grid under-voltage (UV) threshold (restricted range)
Set F>
Grid over-frequency (OF) threshold (restricted range)
Set F<
Grid under-frequency (UF) threshold (restricted range)
Set Uconn>
Max. permissible voltage during checks prior to grid connection
Set Uconn<
Min. permissible voltage during checks prior to grid connection
Set Fconn>
Max. permissible frequency during checks prior to grid connection
Set Fconn<
Min. permissible frequency during checks prior to grid connection
Set Time U>>
Over-voltage U>> protection tripping time
Set Time U<<
Under-voltage U<< protection tripping time
Set Time F>>
Over-frequency F>> protection tripping time
Set Time F<<
Under-frequency F<< protection tripping time
Set Time U>
Over-voltage U> protection tripping time
Set Time U<
Under-voltage U< protection tripping time
Set Time F>
Over-frequency F> protection tripping time
Set Time F<
Under-frequency F< protection tripping time
Set time conn 1 Grid check time prior to connection
Set time conn 2 Grid check time prior to connection after a grid fault
Disable U>>
Disables the U>> protection threshold
Disable U<<
Disables the U<< protection threshold
Disable F>>
Disables the F>> protection threshold
Disable F<<
Disables the F<< protection threshold
Disable U>
Disables the U> protection threshold
Disable
U>
Disables the U> (10Min) protection threshold
(10Min)
Disable U<
Disables the U< protection threshold
Disable F>
Disables the F> protection threshold
Disable F<
Disables the F< protection threshold
U> (10Min) Der. Enables power derating mode due to high average grid voltage readings
Slow Ramp
Enables gradual ramping up of power after the grid connection.
OF Derating
Selects the power derating mode in the event of grid over-frequency.
Time period after OF derating in which the inverter checks that the fre-
quency is back within the operating ranges (parameters Fconn< and
OF Der. Rest. T
Fconn>) required by the grid standard before ramping up the output from
the derating condition
Enables Amorphous Mode in the event that the negative input pole is
Amorph. Enable
grounded by installing the Negative Grounding Kit (not available)
Unlocks the grid standard selection (resets the 24 hours available for chan-
Reset Country S.
ging the grid standard)
The table below shows the parameters that can be changed and the
range of values that may be set for each:
7 - Operation
Setting range
Unom ... Unom x 1.3
10V ... Unom
Fnom ... Fnom + 5Hz
Fnom - 5Hz ... Fnom
Unom ... Unom x 1.3
Unom ... Unom x 1.3
10V ... Unom
Fnom ... Fnom + 5Hz
Fnom - 5Hz ... Fnom
Unom ... Unom x 1.3
10V ... Unom
Fnom ... Fnom + 5Hz
Fnom - 5Hz ... Fnom
0 ... 327670mS
0 ... 65535mS
Enabled/Disabled
0 Derating disabled
1 BDEW derating
2 VDE-AR-N derating
3 CEI derating
1 ... 1000S
Enabled/Disabled
Reset