Technical Specifications - Siemens SIMATIC ET 200SP Equipment Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications

The following table shows the technical specifications as of 11/2022. You will find a data
sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/ww/en/pv/6ES7512-1DM03-0AB0/td?dl=en).
Article number
Product function
Engineering with
Mains buffering
28
General information
Product type designation
HW functional status
Firmware version
I&M data
Module swapping during operation (hot
swapping)
Isochronous mode
STEP 7 TIA Portal configurable/integrated
from version
Configuration control
via dataset
Control elements
Mode selector switch
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Mains/voltage failure stored energy time
Input current
Current consumption (rated value)
Current consumption, max.
Inrush current, max.
I²t
Power
Infeed power to the backplane bus
Power loss
Power loss, typ.
Memory
6ES7512-1DM03-0AB0
 
CPU 1512SP-1 PN
FS01
V3.0
 
Yes; I&M0 to I&M3
Yes; Multi-hot swapping
Yes; only with PROFINET; with minimum OB 6x
cycle of 500 µs
 
V18 (FW V3.0); with older TIA Portal versions con­
figurable as 6ES7512-1DK01-0AB0
 
Yes
 
1
 
24 V
19.2 V
28.8 V
Yes
 
10 ms
 
0.51 A
0.7 A
1.34 A; Rated value
0.3 A²·s
 
8.05 W
 
6.5 W
 
CPU 1512SP-1 PN (6ES7512-1DM03-0AB0)
Equipment Manual, 11/2022, A5E33591411-AE
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu 1512sp-1 pn

Table of Contents