Siemens SIMATIC ET 200SP Equipment Manual page 29

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Article number
Work memory
Load memory
Backup
DB
FB
FC
OB
CPU 1512SP-1 PN (6ES7512-1DM03-0AB0)
Equipment Manual, 11/2022, A5E33591411-AE
Number of slots for SIMATIC memory card
SIMATIC memory card required
integrated (for program)
integrated (for data)
Plug-in (SIMATIC Memory Card), max.
maintenance-free
CPU processing times
for bit operations, typ.
for word operations, typ.
for fixed point arithmetic, typ.
for floating point arithmetic, typ.
CPU-blocks
Number of elements (total)
Number range
Size, max.
Number range
Size, max.
Number range
Size, max.
Size, max.
Number of free cycle OBs
Number of time alarm OBs
Number of delay alarm OBs
Number of cyclic interrupt OBs
Number of process alarm OBs
Number of DPV1 alarm OBs
Number of isochronous mode OBs
Number of technology synchronous alarm
OBs
Number of startup OBs
Technical specifications
6ES7512-1DM03-0AB0
1
Yes
 
400 kbyte
2 Mbyte
 
32 Gbyte
 
Yes
 
25 ns
32 ns
42 ns
170 ns
 
4 000; Blocks (OB, FB, FC, DB) and UDTs
 
1 ... 60 999; subdivided into: number range that
can be used by the user: 1 ... 59 999, and num­
ber range of DBs created via SFC 86: 60 000 ... 60
999
2 Mbyte; For DBs with absolute addressing, the
max. size is 64 KB
 
0 ... 65 535
400 kbyte
 
0 ... 65 535
400 kbyte
 
400 kbyte
100
20
20
20; With minimum OB 3x cycle of 250 µs
50
3
1
2
100
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpu 1512sp-1 pn