Mitsubishi Electric Melservo JE Series Instruction Manual page 175

Servo amplifier, sscnet iii/h interface ac servo with functional safety

Advertisement

7. SPECIAL ADJUSTMENT FUNCTIONS
(b) Switching timing chart
Droop pulses
[pulse]
Gain switching
Load to motor inertia ratio
Position loop gain
Speed loop gain
Speed integral compensation
(3) When the gain switching time constant is disabled
(a) Switching time constant disabled was selected.
The gain switching time constant is disabled. The time constant is enabled at gain return.
The following example shows for [Pr. PB26 (CDP)] = 0103, [Pr. PB27 (CDL)] = 100 [pulse], and [Pr.
PB28 (CDT)] = 100 [ms].
Droop pulses [pulse]
Gain switching
Switching at [Pr. PB28 (CDT)] = 100 [ms] only when gain switching off (when returning)
Command pulses
+CDL
0
-CDL
Before-switching gain
4.00
120
3000
20
Command pulses
+100 pulses
0
-100 pulses
Switching time constant
disabled
Switching at 0 ms
Before-switching gain
7 - 20
Droop pulses
After-switching gain
63.4%
CDT = 100 ms
10.00
84
4000
50
After-switching gain
63.4%
CDT = 100 ms
Command pulses
4.00
10.00
120
84
3000
4000
20
50
Droop pulses
After-switching gain
Switching at 0 ms