Connecting
4.1
Basic safety instructions
Unsuitable cables, cable glands and/or plugs
Risk of explosion in hazardous areas.
● Use only cable glands/plugs that comply with the requirements for the relevant type of
● Tighten the cable glands in accordance with the torques specified in Technical data
● Close unused cable inlets for the electrical connections.
● When replacing cable, glands use only cable glands of the same type.
● After installation, check that the cables are seated firmly.
Incorrect conduit system
Risk of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.
● In the case of a conduit system, mount a spark barrier at a defined distance from the device
Lack of equipotential bonding
Risk of explosion through compensating currents or ignition currents through lack of
equipotential bonding.
● Ensure that the device is potentially equalized.
Exception: It may be permissible to omit connection of the equipotential bonding for devices
with type of protection "Intrinsic safety Ex i".
Unprotected cable ends
Risk of explosion through unprotected cable ends in hazardous areas.
● Protect unused cable ends in accordance with IEC/EN 60079-14.
SITRANS P320/P420 (mA/HART)
Compact Operating Instructions, 06/2018, A5E38874562-AA
WARNING
protection.
(Page 55).
WARNING
input. Observe national regulations and the requirements stated in the relevant approvals.
WARNING
WARNING
4
29