Absolute Pressure With Front-Flush Diaphragm - Siemens SITRANS 7MF03.0 Compact Operating Instructions

Pressure transmitter
Hide thumbs Also See for SITRANS 7MF03.0:
Table of Contents

Advertisement

Effect of mounting position - absolute pressure from gauge and differential pressure series
In pressure per change of angle
● For absolute pressure (from the gauge pressure series):
≤ 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline
● For absolute pressure (from the differential pressure
series): 0.7 mbar/0.07 kPa/0.001015 psi per 10° incline
(zero-point correction is possible with position error compen‐
sation)
7.3.6

Absolute pressure with front-flush diaphragm

Conformity error at limit point setting, including hysteresis and repeatability
Measuring span ratio r (spread, Turn-Down)
Linear characteristic curve
All measuring cells
Effect of ambient temperature
In percent per 28 °C (50 °F)
All measuring cells
Long-term stability at ±30 °C (±54 °F)
All measuring cells
Step response time T
(without electrical damping)
63
Approx. 0.105 s
Effect of mounting position
In pressure per change of angle
0.04 kPa/0.4 mbar/0.006 psi per 10° incline
(zero-point correction is possible with position error compen‐
sation)
SITRANS P320/P420 (mA/HART)
Compact Operating Instructions, 06/2018, A5E38874562-AA
7.3 Measuring accuracy of SITRANS P420
r = max. measuring span/set measuring span and nominal
measuring range
r ≤ 10
≤ 0.2%
≤ (0.16 • r + 0.24)
In 5 years ≤ (0.25 • r)%
Technical data
10 < r ≤ 30
≤ 0.4%
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans p420Sitrans p320Sitrans 7mf04.0

Table of Contents