7. High Temperature and Overload Protection (AP1 below means control board of outdoor unit) E8
Start
If the outdoor ambient temperature is
higher than 53°C?
No
is good?
No
If the indoor and outdoor fan are
running normally?
Yes
Replace outdoor
mainboard
End
54
Normal protection, please use it
Yes
after improving the outdoor ambient
temperature
No
Improve the radiating environment of
unit (clean the heat exchanger and
remove surrounding obstacles)
No
Connect normally?
Yes
Fan capacitor is broken?
No
Motor is broken?
No
Replace mainboard
Service Manual
Unit restarts
Yes
normally
Yes
Unit restarts
normally
Yes
Adjust the
connection
Replace fan
Yes
capacitor
Yes
Replace motor
Installation and Maintenance