R3 Lv Series User Manual 1. Introduction Before installation: 1.1 Introduction This manual describes solar inverters: R3-10K-LV / R3-12K-LV / R3-15K-LV Installation: These inverters are transformerless based inverters. Disconnecting the inverter: 1.2 Applied designations Operating the inverter: should be used.
2.3 Technical data 2.1 Mechanical design Model R3-10K-LV R3-12K-LV R3-15K-LV DC Input Data Figure 2-1 shows the outline dimensions and electrical terminals of R3-10K-LV / R3-12K-LV / R3-15K-LV: 15000 W 18000 W 22500 510.00 185.00 Max. DC Power for Single MPPT...
R3 Lv Series User Manual R3 Lv Series User Manual 2.4 Grid codes National / Regional Grid Code Description General Data 506 386 185mm AS4777 RD1699 Communication Greece -25℃ ~ 60 ℃ Relative Humidity 0 ~ 100% C10/11 < 0.2W China Transformerless BDEW-DE...
R3 Lv Series User Manual R3 Lv Series User Manual 3. Installation and startup Warning! No sun No rain No snow Sunlight Rain Snow Figure 3-2 installation environment Note! 3.3 Installation position 3.1 Package information INVERTER*1 MOUTING PANEL*1 PV CONNETOR(+)*4 PV CONNETOR(-)*4 Figure 3-2 installation position QIG*1...
R3 Lv Series User Manual R3 Lv Series User Manual 3.4 Mounting procedure 3.5 Electrical connection 3.5.1 Connection to the grid (AC output) 400mm 50mm 4- 11Holes,Depth 50mm Connect the inverter to the grid: 1) Scrip off PE/N/L1/L2/L3 cables as figure below: Description Remark Protective layer diameter...
R3 Lv Series User Manual R3 Lv Series User Manual 5) The cables are inserted into the terminal according 6) Insert the main part of AC connector into the 3) Hold the unlocking buckle with one hand and rotate 4) Use a screwdriver to peel off the positions (both to the wire sequence (L1/L2/L3/N/PE), so that the terminal and hear a "click"...
COM1 Figure 3-17 3.5.3.1 WIFI/GPRS Communication (optional) Connect the WIFI/GPRS module produced by Renac to the COM1 port of inverter. After successful connection, information such Figure 3-19 3.5.3.3 DRM connection as power generation and running state of the inverter can be viewed via the App on the phone. The details please refer to the The inverter supports the demand response modes as specified in the standard AS/NZS4777.
R3 Lv Series User Manual R3 Lv Series User Manual 4.2 LCD display 3.6 Starting the Inverter Normal/Fault Pac = Set Language English Factory Set Factory Set Vpv1: Pac = Portuguese Set Country Factory Set Factory Set Ipv1: Pac = The unused terminals are covered.
R3 Lv Series User Manual R3 Lv Series User Manual 4.4 Setting language 253.0V/251.1V 223.3V/1993ms 253.0V/243.9V 223.3V/1993ms 264.5V/232.6V 223.8V/187ms 4.5 Setting modbus address 195.5V/213.0V 223.5V/1485ms 34.5V/36.2V 226.4V/190ms 50.20Hz/49.88Hz 49.98Hz/95ms 4.6 Self-Test in accordance with CEI 0-21 (Applies to Italy only) 49.80Hz/49.88Hz 50.03Hz/88ms 51.50Hz/51.39Hz...
R3 Lv Series User Manual R3 Lv Series User Manual 5.2 Service after warranty expiration Solar Admin COM1 History info Protection other 253.0 224.0 264.5 230.5 195.5 230.2 2000 1987 1500 1486 Pass Pass Pass 34.5 225.0 50.2 50.01 Fmin 49.8 49.94 AUTOTEST...
EEPROM_R Fail Fans Once a year Permanent Fault Cable entry Once a year SciCommLose Electrical Connection BusFault the metal enclosure. CPU ADFault PLLFault Maintenance Instruction AutoTestFail FanError Fan Maintenance 6.2 Maintenance • NOTICE broken fans in time. Renac Power Renac Power...
Page 14