Screen Messages - Gemini Tinytag TGE-0003 Technical Manual

Tinytag energy logger
Hide thumbs Also See for Tinytag TGE-0003:
Table of Contents

Advertisement

12.2 Modes of Operation:
Three Phase Current and Voltage

Screen Messages

Battery Low
The batteries in the logger need replacing.
Checking Coils...
This error message shows for a few seconds after clearing the
"Plug in I1, l2 or l3" message.
Clip I1, I2, and I3
A three-phase current configuration is selected and one or more
of the coils have not been clipped around a conductor. This error
may also be caused by a placement problem.
Connect Mains!
A configuration using the mains connector is selected, but mains
is not connected or has not been switched on.
Mains Voltage Low!
The mains voltage is lower than the minimum operating voltage
(200V).
Over-Current I1, I2, and I3
Instantaneous current levels are too high. The current profile
probably has large spikes exceeding 5,000A (instantaneous).
Alternatively the current may significantly exceed the 2000A RMS
rated range. Logging will continue, but power measurements may
be underestimated.