12.2 Modes of Operation:
Three Phase Current and Voltage
Screen Messages
Battery Low
The batteries in the logger need replacing.
Checking Coils...
This error message shows for a few seconds after clearing the
"Plug in I1, l2 or l3" message.
Clip I1, I2, and I3
A three-phase current configuration is selected and one or
more of the coils have not been clipped around a conductor.
This error may also be caused by a placement problem.
Connect Mains!
A configuration using the mains connector is selected, but
mains is not connected or has not been switched on.
Mains Voltage Low!
The mains voltage is lower than the minimum operating
voltage (200V).
Over-Current I1, I2, and I3
Instantaneous current levels are too high. The current profile
probably has large spikes exceeding 5,000A (instantaneous).
Alternatively the current may significantly exceed the
2000A RMS rated range. Logging will continue, but power
measurements may be underestimated.
22