3.4.9.5. Cabinet dimensions and weight
Length
Depth
Width
Height
3.4.9.6. Braking resistor cables
Cable type
Minimum cross sectional area
Voltage rating
Maximum length
The configuration and dimensions of the braking resistors depend on the specific application.
For information, see the "Dimensioning of braking resistors" application note.

3.5. Cooling system

3.5.1. Fan configurations

The cooling system of the drive is equipped with one of the following fan configurations:
Non-redundant: The fan (1 in Fig. 19) is installed inside the cabinet.
Redundant: Fan 1 and fan 2 (1 and 2 in Fig. 20) are installed on the roof. This configuration
enables continuous operation of the drive if a fan fails.

3.5.2. Type of fan

The drive is equipped with one of the following types:
AC fans: The AC fans are turned on and off with digital signals which switch contactors to
connect or disconnect the 3-phase auxiliary power. The AC fan speed is not controlled.
EC fans: The electronically commutated (EC) fans are controlled via an analog signal from
the drive based on the inverter current. The EC fan speed is controlled depending on the
required cooling.

3.5.3. Starting, stopping the cooling system

The drive switches on the cooling system when the main circuit breaker (MCB) closes. When the
MCB opens, the cooling system switches off after a delay. The delay corresponds to the
discharging time of the drive and takes up to 5 minutes.
PRODUCT
ACS1000A
644 mm
902 mm
2002 (2070 including lifting eyes)
460 kg
Shielded
2
70 mm
Half of maximum converter DC-link voltage
If a multi-core cable is used, the full DC-link voltage must be taken
into consideration.
50 m
DOCUMENT KIND
User manual
POWER ELECTRONICS AND CABINET FEATURES
DOCUMENT ID.
3BHS213401 E01
REV.
LANG.
PAGE
L
en
41/164