• Follow the prescribed electrostatic discharge (ESD) prevention procedures to prevent damaging the
equipment. Static discharge can cause components to fail completely or intermittently over time.
• Install the device in a secure area, so that only authorized personnel can access the device.

Site Electrical Wiring Guidelines

Table 20 on page 51
describes the factors you must consider while planning the electrical wiring at
your site.
WARNING: You must provide a properly grounded and shielded environment and use
electrical surge-suppression devices.
Avertissement Vous devez établir un environnement protégé et convenablement mis à
la terre et utiliser des dispositifs de parasurtension.
Table 20: Site Electrical Wiring Guidelines
Site Wiring
Guidelines
Factor
Signaling
If your site experiences any of the following problems, consult experts in electrical surge
limitations
suppression and shielding:
Improperly installed wires cause radio frequency interference (RFI).
Damage from lightning strikes occurs when wires exceed recommended distances or pass
between buildings.
Electromagnetic pulses (EMPs) caused by lightning damage unshielded conductors and
electronic devices.
Radio
To reduce or eliminate RFI from your site wiring, do the following:
frequency
Use a twisted-pair cable with a good distribution of grounding conductors.
interference
If you must exceed the recommended distances, use a high-quality twisted-pair cable with
one ground conductor for each data signal, when applicable.
51