Midea LC3 Series Technical & Service Manual page 97

Dc inverter air conditioner
Table of Contents

Advertisement

MCAC-UTSM-202006
Manual
90/105/140/160
Sequence
Spot check parameter contents
number
01
Operating mode
02
Operating wind speed and level
03
The capacity of Indoor unit(HP)
The total capacity demand of
04
indoor unit
The capacity demand after
05
correction of outdoor unit
06
Ts setting temperature
07
T1 Indoor temperature
08
T2 or T2B temperature
09
T3 piping temperature
10
T4 ambient temperature
11
T5 discharge temperature
12
TF module temperature
TL refrigerant heat sink pipe
13
temperature
The opening of EXV
14
The actual current
15
The compressor current
16
17
The actual voltage
18
The DC bus voltage
19
Model type
The network address of Indoor
20
unit(0-63)
The address of outdoor unit in
21
centralized control
system(reserved)
The number of Indoor unit
22
program version
The number of outdoor unit
23
program version
24
The last error code
25
Display --
26
Read indoor unit SN code
Midea LC3 Series DC Inverter Air conditioner Technical Service
Remarks
0:Standby;1:Fan only;2:Cooling;3:Heating;4:Forced
Cooling;6:dehumidification
0:OFF;1:Low speed;2:Middle speed;3:High speed
Actual value
Actual value
Actual value (Display T2 in heating mode; display T2B in other
modes)
Actual value
Actual value
Actual value
Actual value
Actual value
Actual value×8
Actual value
Actual value
0-7 is valid
Display "E-" if not existing
96