Midea LC3 Series DC Inverter Air conditioner Technical Service Manual
MCAC-UTSM-202006
105/140/160
Error code
Error definition
HF
IDU mismatching error
L (L0/L1) error occurs three times in one hour,
reporting H4,and this error is not recoverable.
After H4 error, spot check may be performed on
H4
the latest three L errors (not limited to L0, L1).
For example: report L0-L4-L8-L9-L0-L1 within
one hour, and report H4 error.The errors for
spot check are L9, L0, and L1.
E7
IDU EEPROM error
E9
ODU EEPROM error
Wrong
E.9.
memory EPROM
Communication error between main control
H0
board and IR341
E1
Communication error between IDU and ODU
E2
T1 sensor error
E3
T2 sensor error
E4
T2B sensor error
E43
T3 sensor error
E44
T4 sensor error
E45
T5 sensor error
E5
Voltage protection error
E6
ODU DC fan error
EE
Water level alarm error
Ed
Rest of ODU error(EE,LA,LC,LH etc)
E6 error occurs six times in one hour, requiring
Eb
power failure recovery
EF
PFC feedback resistance failure
PL
Heat sink TF high temperature protection
P1
High pressure protection
P2
Low pressure protection
P3
Input current protection
P4
Discharge temperature protection
Outdoor
P5
protection
PE
Evaporator T2 high temperature protection
L0
Module protection is triggered
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error
L5
Zero speed protection
L7
Phase loss
Protection when the previous and next speed
L8
change is > 15Hz
compressor
model
condenser
T3
high
Error display
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
in
parameter
Immediate display (Display E9), spot check
available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Immediate display, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Immediate display, spot check available
Display after 10 minutes, spot check available
Immediate display, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
temperature
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
Display after 10 minutes, spot check available
93