Midea LC3 Series Technical & Service Manual page 96

Dc inverter air conditioner
Table of Contents

Advertisement

Midea LC3 Series DC Inverter Air conditioner Technical Service Manual
MCAC-UTSM-202006
2. Spot check query function (Press the button on the display board to spot check the system
parameters)
26/35/53/71
Sequence number
Spot check parameter contents
01
Indoor unit T1 temperature
02
Indoor unit T2 temperature
03
Outdoor unit T3 temperature
04
Outdoor unit T4 temperature
05
Outdoor unit TP temperature
06
Outdoor unit IPM temperature
07
Current compressor target frequency
08
Current compressor operating frequency
Current operating wind speed of internal
09
fan
Current operating wind speed of external
10
fan
Opening of electronic expansion valve of
11
outdoor unit
12
Voltage
13
current
14
Indoor unit program version number
Indoor unit EEPROM parameter program
15
16
Machine model
17
the last fault code
18
the last but one fault code
19
the last but two fault code
20
nd
version number
Remarks
Actual value, temperature accurate to 0.5 ℃
Actual value, temperature accurate to 0.5 ℃
Actual value, temperature accurate to 0.5 ℃
Actual value, temperature accurate to 0.5 ℃
Actual value, it can display three digits such as
101 ℃
Actual value, temperature accurate to 0.5 ℃
Actual value
Actual value
Actual value×10
Actual value×10
No electronic expansion valve,it shows "0"
Actual value
Actual value
No fault display "--"
No fault display "--"
No fault display "--"
End