Dell PowerEdge FC630 Owner's Manual page 110

Hide thumbs Also See for PowerEdge FC630:
Table of Contents

Advertisement

Environmental specifications
NOTE: Applies to data center environments
only. Air filtration requirements do not
apply to IT equipment designed to be used
outside a data center, in environments such
as an office or factory floor.
Conductive dust
NOTE: Applies to data center and non-data
center environments.
Corrosive dust
NOTE: Applies to data center and non-data
center environments.
Gaseous contamination
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate
Silver coupon corrosion rate
Expanded operating temperature
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be
reported on the LCD and in the System Event Log.
Continuous operation
< 1% of annual operating hours
110
Air must be free of conductive dust, zinc whiskers,
or other conductive particles.
Air must be free of corrosive dust.
Residual dust present in the air must have a
deliquescent point less than 60% relative
humidity.
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.
5°C to 40°C at 5% to 85% RH with 29°C dew point.
For temperatures between 35°C and 40°C, de-
rate maximum allowable temperature by 1°C per
175 m above 950 m (1°F per 319 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew
point.
Get other manuals https://www.bkmanuals.com
NOTE: Air entering the data center must
have MERV11 or MERV13 filtration.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate continuously down to 5°C or as high
as 40°C.
NOTE: Outside the standard operating
temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.