5.2.2 LF622 Type
The terminal board connections of separate type converter LF622 are shown in Figure 5.1. Proceed with
wiring as described in Section 5.4, "Wiring Procedure."
LF622
Instrument panel : Ordered separately
Grounding with 100Ω or less
ground resistance
Power switch
(External double-pole power switch)
Power supply
Current output (4〜20mAdc)
or PROFIBUS
Digital input (20〜30Vdc)
or Modbus
Digital output 2
Signal common for DI and DO
Digital output 1
Grounding with 100Ω or less
ground resistance
NOTE:
To avoid 2-point grounding, ground
the shield of the output cable basically
at the receiving side.
I/O cable
(CVV-S)
Figure 5.2 External Wiring Schematic Diagram
− 23 −
Power cable
(CVV)
NOTE:
• When 3-core power cable is used, do not ground from
the external grounding terminal. Perform grounding at
the receiving side only.
• Only when a 2-core power cable is used, perform
grounding from the external grounding terminal.
6 F 8 A 0 9 2 7
Ⅳ wire 5.5mm
NOTE
or more
Grounding with 100Ω or
less ground resistance
Thick conduit tube
Signal cable
(2-core shielded
cabtypre cable)
Excitation cable
(3-core cabtypre
cable)
Detector
2