12.2 Output Status for Errors and Alarms

Error indication
ROM ERROR 
(Note 1)
RAM ERROR 
PARAMETER 
FAILURE 
 (Note 2)
EXC CUR 
OPEN 
EXC CUR 
ERROR 
ADC ERROR 
INVALID 
TOTAL 
HIGH ALARM 
LOW ALARM 
HIGH HIGH 
ALARM 
LOW LOW 
  ALARM 
Note 1: The display and output may not be correct depending on the nature of the ROM error.
Note 2: If a parameter failure relating to the current output occurs, the current output may not become
the value as specified by the setting when an alarm occurs.
Note 3: The current output value used in case an alarm occurs will be output. For setting method, see
8.2.16, "4−20mA Alarm Output Setting."
Measured value
Current output
indication
(4-20mA)
Zero
Zero
Zero
Zero
Measured data
Measured data
Measured data
Measured data
Measured data
Measured data
Measured data
Measured data
Measured data
Measured data
− 140 −
Totalization
pulse output
(Note 3)
Stopped
(Note 3)
Stopped
(Note 3)
Stopped
(Note 3)
Stopped
(Note 3)
Stopped
(Note 3)
Stopped
Measured data
Measured data
Measured data
Measured data
Measured data
6 F 8 A 0 9 2 7  
Remarks
After power-up,
no measurement starts.
After power-up,
no measurement starts.
―――――――
Still water zero adjustment
cannot be performed.
Still water zero adjustment
cannot be performed.
Still water zero adjustment
cannot be performed.
The error message
disappears if you clear
(reset) the totalizer count.
―――――――
―――――――
―――――――
―――――――