Chapter 6 Operation - Hitachi SJ-FB Instruction Manual

Feed-back board
Hide thumbs Also See for SJ-FB:
Table of Contents

Advertisement

Refer to [Chapter 3 OPERATION] in the instruction manual for the SJ300 inverter before operating
with this board. When the operation command is given from the terminal side of the inverter main
body, operate with the following procedure.
<Procedure>
1. Turn ON the POWER switch of the inverter.
2. Set the control method (A044) in [05].
3. Set the necessary items according to the instruction manual "Chapter 4 FUNCTION
EXPLANATION" of the inverter main body.
4. For speed control, operation is started when operation command of the inverter main body
is turned on.
5. For position control, turn on the STAT terminal of SJ-FB and operation command of the
inverter main body first of all. Next input the pulse train position command to SAP-SAN
and SBP-SBN. Then the motor turns only the pulse that you input.
Confirm the following while trial operation.
The motor accelerates normally.
The motor rotates in the correct direction.
Neither abnormal vibration nor noise is recognized in the motor.
If the motor doesn't accelerate normally or the inverter trips with overload, check the encoder for
phase order.
Phase order : The normal phase order is that the waveform of phase A advances by 90°
than that of phase B when the motor rotates forward.
(Note 1) : The monitor signal may not be output from FM terminal of inverter main body under
vector control with sensor (A044=05). Please confirm the monitor output in this case.
(Note 2) : Please do not do the free run action by "RS terminal" of inverter main body. When you do
this action, over current trip, or power element destruction may occur. Please use "FRS"
the terminal when performing free run action.
(Note 3) : If the torque limit setting (b041-b044) is enlarged, over current trip would occur at the
time of the motor added burden. In this case, please adjust the torque limit setting value.
(Note 4) : The motor constant data of the SJ300 series is the data at the time of base frequency 50Hz
in the J1 motor made in Hitachi. . Please put in the value that did it to motor constant
I0 (H023) 0.7 times, in the case that you use it with base frequency 60Hz in the J1
motor.
(Note 5) : Please do the auto tuning, in the case that you do not understand the motor constant.
19
Get other manuals https://www.bkmanuals.com
Chapter 6
OPERATION

Advertisement

Table of Contents
loading

Table of Contents