4.1
Power supply working range
Nominal power supply
◆
• Single phase: ~ 230V 50Hz
• Three phase: 3N~ 400V 50Hz
Operating voltage
◆
Between 90 and 110% of the nominal voltage.
Voltage imbalance for nominal power supply 3N~ 400V 50Hz
◆
Up to 3% of each phase, measured at the main terminal of the outdoor unit.
Starting voltage
◆
Always higher than 85% of the nominal voltage.
4.2
R32 Temperature working range
MODEL
Water temperature
Indoor ambient temperature
4.2.1 Space heating
60
50
45
40
30
20
10
0
-30
-25
-20
-10
Ambient temperature (°C)
PMEN0643 rev.0 - 04/2023
°C
-5
0
10
20
1.5HP
2.0HP
Refer to the graphics for each case
Continuous working range
Starting heat pump + back up heater
Starting only back-up heater
operation
Marked areas with
available if back-up heater is enabled.
25
30
2.5HP
3.0HP
5~30
and
only
4
13